l
Page 14
Kaval Telecom Inc.
DCM000000001
•
Battery
This Menu allows the user to tell the controller whether a backup battery is installed (Yes/No), and allows setting of
battery voltage thresholds. If not installed, then no battery faults will signal, and no voltage display is shown.
Battery Menu
Batt. Installed? Yes
Low Voltage: 24.0
Warn Voltage: 21.5
Cutoff Voltage: 21.0
•
Controller Menu
This Menu allows the user to display the Software Revision, change the Password, perform a Lamp Test, control the
Buzzer and reset to Factory Settings.. Pressing select key with Lamp test shown causes a test pattern to be shown
on the VFD, and all LEDs light up all at once, then are lit individually in sequence. If the Factory Defaults function is
selected, a confirmation screen appears asking the user to toggle the entry to yes and hit select before memory is
cleared. Selecting “Set Password” allows user to enter a new password. The entry must be made a second time to
confirm. In this case, display says “Confirm password”. If password is set to 000, then no password check is done
(factory default). If password is forgotten, then EEPROM in controller must be replaced. Controller menu entries are:
Software Rev: 1.3
Set Password
Lamp Test:
Beep: Yes
Factory Defaults?Yes
•
Calibration Menu
This Menu is for future use by the Kaval Factory only, and should not be used.