Menu 2 - Service
Overview
Menu 2 - Service
Step
(informative)
Max
Time
Current
(informative)
Max
Marginal
Effect factor
S.time test
Menu 3 - Test manually
Menu 4 - Setup
Menu 2.1 Step
Currently used power step. Informative reading.
Menu 2.1.1 Max
Maximum number of allowable power steps. Settable value:
Setting range for models 112 kW and below 0 - 7
Default value 7
Setting range for models 112 kW and above 0 - 15
Default value 15
Note! This setting prevents the boiler to use higher power steps i.e. limits the power of the boiler.
Menu 2.1.2 Time
Used step time for increasing power i.e. at least this time is spent between enabling next power step.
Settable value:
Setting range 20 - 250 s
Default value 90 s
Note! Too short step time can cause constant fluctuation.
Fluctuations can be eliminated by decreasing or increasing the step time, depending on the pump capacity
and water volume. Sufficient flow in the boiler at all times ensures stable control.
Menu 2.2 Current
Currently measured highest phase current of main fuses. Configure Menu 2.2.1 Max and Menu 2.2.2
Marginal for using load monitor property. Informative reading.