10.4
Alarm Screen
Change back to the Screen «Overview»
Reset Alarm’s
Alarm’s
Alarms
Flow Low
Flow rate through EK below 0.5 m^3/h
Voltage High
Voltage on the Activator is above 21.5 V DC.
Voltage Low
Voltage on the Activator is below 0.25 V DC.
Temperature High
Cabinet temperature (internal) is above 45°C
Overvoltage
Electrical circuit to the Activator is open
Short Circuit
Short circuit inside of the Activator or the wiring
to the Activator
Communication Error
Connection between PLC and HMI is faulty
Switches on the Screen “Alarm”
Change to the screen “Overview.”
Acknowledge all Alarms.
Red LED will disappear when no alarms are pending