DN1769-1809
27
Kantech Telephone Entry System Installation Manual
STEP 18: Connecting the Ethernet Cable (Optional)
Connect the Ethernet cable to the RJ-45 port.
•
The TXRX (YELLOW) LED is OFF when there is no Ethernet network or the cable is disconnected;
FLASHING when there is network activity; and ON when the network is present
•
The 100 (GREEN) LED is ON only when the KTES is connected to a 100 Mb/s (100 Base-T) network.
STEP 19: Powering Up the KTES
Once powered, check the blue heartbeat LED status indicator to determine the status of communication and other
vital parameters. Refer to the troubleshooting section for the patterns. If the main supply is removed, the 12 VDC,
7 A/h backup battery will support normal operation.
Important:
The KTES will not start on backup battery alone.
STEP 20: Programming the KTES
If you intend to program the KTES remotely with an access control software like EntraPass, there are some
options that must be done with the VUI before leaving the customer premises.
Enter the KTES programming mode by pressing and holding
during 5 seconds, until you hear a beep. Type in
the
Installer PIN (8888)
.
Important:
For security reasons, keep in mind to change the default installer PIN (8888) after the
installation and
configuration are completed
and give it to the owner or the maintenance dept of the building. Refer
to the Tenant Menu in the
KTES Programming Manual,
DN1770.
Options only Programmable with the VUI
Note:
For more information on how to configure the KTES with the VUI, refer to the
KTES Programming Manual
,
DN1770.
Option Name
Keypad Shortcut
Audio Visual > Speaker Volume
8-1-2-2-1
Audio Visual > Microphone Sensitivity
8-1-2-2-2
Audio Visual > Telephone Sensitivity
8-1-2-2-3
Audio Visual > LCD Contrast
8-1-2-2-4
Audio Visual > Live Adjustment
8-1-2-2-5