K T - 1 0 0 I n s t a l l a t i o n M a n u a l
3
S e c t i o n 1 : K T - 1 0 0 F e a t u r e s
The KT-100 Door Controller contains all the intelligence and
necessary inputs/outputs to manage one door; it is also easily
linked to a network controlling up to 32 doors.
The KT-100 Door Controller features include:
Speed selection.
The
KT-100 automatically detects the loop
communication speed as set at the system workstation.
Trouble reporting.
The KT-100 constantly supervises
power supply conditions and reports “Low power” status to the
system. The power output is protected against short-circuits and
surges by a self-resetting PTC. The locking device is supervised
for short to ground or open circuits. It also monitors all the
equipment for any failure or tampering. Any abnormal
condition is reported to the software.
Downloadable firmware.
The firmware program is
stored in the controller’s flash memory; it can be easily updated
from the system’s workstation without changing the memory
chips.
Integration with a client alarm system.
The KT-100
Controller allows the ability to arm/disarm any client alarm
system. In addition, interfacing with an external alarm system
allows the installer to assign the appropriate user permission to
arm or disarm the external alarm system. Optionally, adding a
keypad will increase the security as cardholders will be required
to enter a valid code in addition to presenting a valid card at the
door reader. For details about using the KT-100 Controller to
interface another alarm panel, refer to “Using the KT-100 with
an external alarm panel” on page 12.
Te c h n i c a l S p e c i f i c a t i o n s
Input power
9.5 to 14 VDC / 50mA + accessories (Max. 750 mA)
Dimensions (H•W•D)
11.4 cm x 7.0 cm x 3 cm (4.5”; 2.75”; 1.25”), mounted
in a standard single gang electri-
cal box without any additional enclosure
Weight
110 g (0.22 lbs)
Operating temperatures / Humidity range
From 2
0
C to 40
0
C (35
0
F to110
0
F) / 0-95% (non-condensing)
Reader types
Wiegand, proximity, bar code, magnetic, integrated keypad and others
Control relay outputs
2 relay outputs, 12VDC, 25mA max/each. Open collector to ground (use form C relays such as
Kantech/KT-RM1 if needed)
2 control relay outputs, 30VAC/DC, 50mA (max) each. Two Opto-isolated contacts per relay
Monitored input zones
4 monitored input zones, NO/NC, with or without end of line resistors
Points maximum wiring
600 meters (2,000 feet) - (AWG #22)
Door strike output
1 form C output, 12VDC, 250 mA max, supervised
Auxiliary outputs (LED, BUZ)
2 outputs, open NPN collector for door access and status 25mA max, 12 DC each
Reader power output
5VDC @ 150mA protected
Communication port
RS-485
Communication speed
From 1200 to 115,200 baud (automatic detection)
Reader communication interface
ANSI, SIA, ABA clock and data, Wiegand 5 conductor
Flash memory
64 K
RAM memory
128 K
Backup battery
Lithium battery, up to 10 years retention (data and RTC operation)
Network autonomy
Distributed data and processing
Certifications / Listing
FCC Part 15, Class B