KANE455 manual
Page 13
4.
USING THE ANALYSER:
4.1 COMBUSTION
TESTS:
Insert the tip of the flue probe into the centre of the flue. The readings will stabilise
within 60 seconds assuming the boiler conditions are stable.
The rotary switch can be used to display the following information:
RATIO Display
NAT GAS
→
Fuel type can be changed via “Menu”.
R 0.0008
→
CO/CO
2
ratio.
COp
52
→
Carbon monoxide (ppm).
CO
2
%
6.3
→
Carbon dioxide (%).
Press
/
to print a full combustion test, (or send to PC via optional
Bluetooth).
Hold
/
for 2+ seconds to log a full combustion report.
O2/EFF display
O
2
%
9.8
→
Oxygen (%) left after combustion. Should be
20.9% ± 0.1% in fresh air.
TFc
145.1
→
Flue temperature (
o
C).
TIc
5.4
→
Inlet temperature (
o
C). Normally set by flue
probe during fresh air purge.
EfC
91.3
→
‘Net’, ‘Gross’ or ‘Condensing’ efficiency (%)
can be selected via “Menu”.
For latest prices and delivery to your door visit MyTub Ltd - www.mytub.co.uk - [email protected]