background image

KS 1200i 
KS 2100i 
KS 3500i
KS 3500iE G-Profi
KS 7100iE G-Profi

Inverter Generator

Please, read this manual 

carefully before use!

Owner’s Manual

KS 2000i S
KS 3300i S
KS 3300iEG S-Profi
KS 4000iE S
KS 4000iEG S-Profi
KS 7200iEG S-Profi

Inverter Generator 

in Soundproof Housing

ENG

Summary of Contents for KS 1200i

Page 1: ...Profi KS 7100iE G Profi Inverter Generator Please read this manual carefully before use Owner s Manual KS 2000i S KS 3300i S KS 3300iEG S Profi KS 4000iE S KS 4000iEG S Profi KS 7200iEG S Profi Invert...

Page 2: ...AND COMPONENTS OF INVERTER GENERATOR KS 7200iEG S Profi 18 12 GENERATOR SPECIFICATIONS 19 22 13 FUNCTIONAL DESCRIPTION OF INVERTER GENERATORS 23 14 TERMS OF USE OF INVERTER GENERATOR 26 15 GENERATOR O...

Page 3: ...configuration and construction The images and drawings in this manual are for reference only and may differ from the actual components and inscriptions on the products Contactinformationthatyouarefre...

Page 4: ...irect contact with grounded surfaces pipes radiators etc _Protect the generator from moisture Water inside the generator increases the risk of electric shock _Be careful when working with the power co...

Page 5: ...rpose only Proper operation of the generator as intended allows better and safer performance _To prevent inhalation of exhaust gases do not operate the generator under conditions of poor ventilation E...

Page 6: ...not touch the generator with wet or dirty hands h _Observe fire safety regulations do not operate the generator near open flame i _ Do not touch The generator dampener becomes hot during operation a...

Page 7: ...cations The OPEN positionmeansopenandthe CLOSE position means closed Indicates the direction of opening the air choke The icon on the left indicates that the fuel tank is full The icon on the right in...

Page 8: ...5 OVERVIEWANDCOMPONENTSOF INVERTERGENERATORS KS1200i KS2100i 2 1 3 5 4 7 1 Overload indicator red 2 Voltage indicator green 3 Oil level indicator yellow 4 Engine start button ON OFF 5 Economycontrolsw...

Page 9: ...itch C N 6 Ground terminal 7 12V 5A DC outlet 8 DC fuse 9 2x16 AC outlets 6 1 2 7 8 9 5 Fig 3 KS2100iCONTROLPANEL Themanufacturerreservestherighttomakechangesintheproduct design configurationandconstr...

Page 10: ...IEWANDCOMPONENTSOF INVERTERGENERATORKS2000iS 1 Fuel tank cap 2 Carrying handle 3 Plug service cover 4 Control panel 2 1 3 4 Fig 4 5 Service cover 6 Manual starter 7 Fuel valve 8 Vent grid 9 Damper 5 8...

Page 11: ...ngine start button ON OFF 7 12V 8A DC outlet 8 12V DC fuse 9 2x16 AC outlets 1 2 3 4 8 6 7 9 5 Fig 5 KS2000iSCONTROLPANEL Themanufacturerreservestherighttomakechangesintheproduct design configurationa...

Page 12: ...panel 1 Engine start button ON OFF 2 Economy control switch C N 3 Multifunction display 4 12VDCfuse 5 Groundterminal 6 12V 8ADCoutlet 7 2x16 ACoutlets 7 OVERVIEWANDCOMPONENTSOF INVERTERGENERATORS KS3...

Page 13: ...y control switch C N 2 Generator parallel socket 3 12V DC fuse 4 Multifunction display 5 Start switch 6 Ground terminal 7 12V 8A DC outlet 8 2x16 AC outlets 7 8 2 3 1 KS 3300iEG S Profi CONTROL PANEL...

Page 14: ...uel valve 8 Gas connection 1 Engine start button ON OFF 2 Economy control switch C N 3 Multifunction display 4 12V 8A DC outlet 5 12V DC fuse 6 Ground terminal 7 1x16 AC outlet 8 OVERVIEWANDCOMPONENTS...

Page 15: ...t switch 2 Economy control switch C N 3 Multifunction display 4 12V 8A DC outlet 5 12V DC fuse 6 Ground terminal 7 1x16 AC outlet 8 Generator parallel socket 1 2 3 4 5 6 8 7 Fig 11 KS3500iEG ProfiCONT...

Page 16: ...l panel 1 _2x16 ACoutlets 2 _Multifunctiondisplay 3 _Startswitch 4 _Economycontrolswitch C N 5 12VDCfuse 6 2V 8ADCoutlet 7 Groundterminal 8 Fuelvalve 9 OVERVIEWANDCOMPONENTSOF INVERTERGENERATORS KS400...

Page 17: ...6 AC outlets 2 Display 3 Start switch 4 Economy mode switch 5 12V DC fuse 6 12V 8A DC outlet 7 Ground terminal 8 Fuel valve 9 Generator parallel socket 6 5 4 2 1 7 8 Fig 14 KS4000iEG S ProfiCONTROL PA...

Page 18: ...AND COMPONENTS OF INVERTER GENERATOR KS 7100iE G Profi 8 7 2 1 3 4 6 1 230V AC fuses 2 Generator parallel socket 3 12V 8A DC outlet 4 Multifunction display 5 Start switch 6 Economy control switch C N...

Page 19: ...TS OF INVERTER GENERATOR KS 7200iEG S Profi 6 1 2 4 5 3 10 5 6 8 9 2 4 1 3 7 1 230VACfuses 2 12VDCfuse 3 12V 8ADCoutlet 4 Multifunctiondisplay 5 Economycontrolswitch C N 6 Groundterminal 7 Start switc...

Page 20: ...Net dimensions L W H mm 310 310 380 375 340 405 Gross dimensions L W H mm 335 330 415 410 380 435 Battery Ah Net weight kg 13 18 Protection class IP23M Nominalvoltagetolerance max 5 To ensure reliabil...

Page 21: ...el Lpa Lwa dB 58 83 58 83 58 83 Output 12V A 8 3 8 3 8 3 Engine model KS 125i KS 170i KS 170i Engine power hp 3 26 6 16 6 16 Crankcase volume cm3 0 35 0 45 0 45 Engine volume cm3 105 149 149 Engine ty...

Page 22: ...dB 69 94 69 94 69 94 Output 12V A 8 3 8 3 8 3 Engine model KS 230i KS 230i KS 430i Engine power hp 5 9 5 9 11 5 Crankcase volume cm3 0 45 0 45 1 1 Engine volume cm3 207 207 406 Engine type Gasoline p...

Page 23: ...level Lpa Lwa dB 58 83 58 83 58 83 Output 12V A 8 3 8 3 8 3 Engine model KS 290i KS 290i KS 430i Engine power hp 6 7 6 7 11 5 Crankcase volume cm3 1 0 1 0 1 1 Engine volume cm3 270 270 406 Engine type...

Page 24: ...the Parallel Unit Parallel connection of two identical generator models ensures double nominal output power of these models When connecting generators of different capacities using the Parallel functi...

Page 25: ...ating mode of the generator from TURBO to ECON and vice versa When the ECONOMY MODE switch is set to OFF the TURBO function is turned on for 60 seconds to enable equipment that requires more power to...

Page 26: ...i KS 4000iEG S Profi KS 7100iE G Profi KS 7200iEG S Profi have control panel equipped with a L D display Once the generator has started the L D display will light up Once you have connected the power...

Page 27: ...t up current ratio of 2 3 This means that the operation of such appliances requires a generator the power of which is 2 3 times the power of the connected power consumer Power consumers such as compre...

Page 28: ...at startup When starting the generator for the first time when the entire system is completely empty be sure to close the air choke so that the system can pump fuel faster During any subsequent startu...

Page 29: ...t your nearest K nner S hnen service center 16 CHECK BEFORE GETTING STARTED CHECKINGTHE FUEL LEVEL 1 Unscrew the fuel cap and check the fuel level in the tank 2 Fill the fuel tank to the fuel filter l...

Page 30: ...tor is used in a confined space since its cooling performance decreases 17 GETTING STARTED Before starting the engine make sure that the power rating of power consumers matches that of the generator D...

Page 31: ...do not release it abruptly _When starting the generator hold the generator by the carrying handle to prevent the generator from falling _Slowly turn the air choke control knob to the OPEN position an...

Page 32: ...sition for 1 3 seconds before starting the generator 13 Slowly turn the air choke to the OPEN position 14 Allow the generator to run idle for 2 minutes 15 Connect the necessary devices to the generato...

Page 33: ...ices to the generator make sure that they are turned off _Beforeturningonthegenerator makesurethatallelectricaldevices including wires and plugs are in good condition _After starting the generator mak...

Page 34: ...chargingcurrentistoohigh Donotchargebatteriesiftheircurrentconsumption is more than 5 8A depending on the generator model PLEASE NOTE Follow the instructions in the battery manual to determine when t...

Page 35: ...acturershallnotbeliablefordamageand loss caused by failure to comply with safety and maintenance regulations THIS PRIMARILY APPLIESTOTHE _Use of lubricants fuels and motor oils not authorized by the m...

Page 36: ...h a hexagon key 5 Wait for the oil to drain Tilt the generator for a better result 6 Screw in the oil drain cap 7 Add motor oil to a high level Recommended motor oils SAE10W 30 SAE10W 40 Recommended m...

Page 37: ...the generator on a flat surface and remove the spark plug cap to prevent the engine from starting Do not start the engine in an enclosed or poorly ventilated area The work area must be well ventilated...

Page 38: ...irfiltermustbereplacedevery50 hoursofoperationofthegenerator inconditionsofincreasedpollution every10hours PLEASE NOTE Fig 28 A spark plug is an important element that ensures proper engine operation...

Page 39: ...e flame arrester 6 Replace the screen and cover of the damper 7 Replace the cover and tighten the screws Matchtheprotrusionoftheflamearrestertotheholeinthepipedamper PLEASE NOTE The engine and damper...

Page 40: ...t so that the inlet and drain valvesgetclosed Cleanthegeneratorfromdirtanddust When starting the generator after long term storage proceed as above in the reverse order 27 GENERATOR AND BATTERY DISPOS...

Page 41: ...line Engine overheating Coolingfinsarecontaminated Cleanthecoolingfins Air filter is dirty Replace the air filter Engine starts but no output voltage Circuit breaker tripped SetthecircuitbreakertoON o...

Page 42: ...idge 100 150 TV set 100 400 Perforator 600 1400 Drill 400 800 Freezer 100 400 Grinder 300 1100 Circular saw 750 1600 Crank gear 650 2200 Jigsaw 250 700 Planer 400 1000 Compressor 750 3000 Water pump 7...

Page 43: ...Ifproperoperationoftheproductcanberestoredfollowingcleaningfromdustand dirt appropriateadjustment maintenance oilchange etc _ Iftheproductisusedforbusinessrelatedpurposes _ Iffaultsaredetected whichha...

Page 44: ......

Page 45: ...___ ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________...

Page 46: ...Deutschland DIMAX International GmbH Deutschland Hauptstr 134 51143 K ln www ks power de info dimaxgroup de KONTAKTDATEN...