11

During generator operation:

- You may use the generator, if the voltage meter displays the value 230V+/- 10% 
(50 Hz) and 400V+ / - 10% (50 Hz) for three-phase generator.
- Watch the voltage meter and in case of excessive indices values, stop the 
generator operation.
- Connection to continuous voltage socket is used for accumulator recharge only. 
Upon accumulator unit recharge, it is mandatory to verify the polarity correctness 
( + to +, - to - ).
- Charging device wires have to be at first connected to the accumulator unit 
and only then – to the generator itself. All “generator to network” connections 
are to be carried out by a certified electrician. Any mistakes may result in serious 
equipment damage.
- It is forbidden to use 12V voltage simultaneously with 230V (400V for three-
phase generators).

In order to stop the engine, perform the following actions:

1. Stop all power consuming devices connected to the generator, set the emergency 
switch to OFF.
2. Let the generator run at no load for 3 minutes for alternator to be cooled.
3. In case of manual start – set the engine switch to OFF position.
4.  In case of electric start, turn the key to OFF position.
5. For all types of diesel generators there is an emergency stop lever for the 
engine. Use it in case of emergency only.

Commissioning

The first 20 hours of generator work please comply the following requirements:
1 During commissioning, do not connect the load which power exceeds 50% of the 
nominal (working) generator power.
2. Change the oil after commissioning. Its better to drain it before the engine cools 
down after work, in this case oil will drain faster.

Connecting devices

After starting the engine, make sure the voltmeter readings correspond to the 
nominal (at 50 Hz 230V + - 5% for single-phase units and 400 + -% for three-
phase).

For three-phase diesel generator

Three-phase diesel generator load must be distributed on all three phases, and 
the load on all phases must be balanced. The load on 1 phase should not exceed 
1/3 of the total generator capacity. Maximum permissible imbalance is 20%. 

Only 1 or 2 phase load leads to the generator breakage. The total load and total 
current on all three phases should not exceed nominal load and current of the 
generator.

Summary of Contents for KSB 6000D

Page 1: ...ENG Diesel Generator Silent Diesel Generator KSB 6000D KSB 6000DE KSB 8000DE ATSR KSB 8000DE 3 KSB 6000DES Please read this manual carefully before use OWNER S MANUAL...

Page 2: ...ded oils _ _ _ _ _ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _17 12 Air filter maintenance _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _18 13 Fuel filter technical maintenance _ _ _ _____________19 14 Accumulator ma...

Page 3: ...nd photos of the product may vary from its actual appearance At the end of this manual You may find contact information which you are free to use in case of any issues occurrence Alldata specifiedinth...

Page 4: ...n working with power cables Immediately replace it in case of damage as damaged wire increases the risk of electric shock All connecting the generator to the network must be made by certified electric...

Page 5: ...operating make sure that the generator is on a flat level surface and the engine switch is set to Off Keep the generator dry well ventilated place if you are not using it Check the connection of movi...

Page 6: ...urring obligation The pictures in this manual are schematical and may not match the parameters of original product IMPORTANT 1 9 2 3 5 4 8 6 7 1 Reinforced steel frame 2 Fuel tank cap 3 Air filter 4 A...

Page 7: ...1 65 1 65 1 65 1 65 Enginecylindervolumecm3 406 406 406 455 455 Power output controller AVR AVR AVR AVR AVR Engine start electric manual manual electric manual electric manual electric Power factor c...

Page 8: ...currents when choosing a generator Most electric tools have starting current ratio 2 3 This means that when you turn such tools required generator power have 2 3 times more power load The biggest fac...

Page 9: ...ENANCE PANEL Pic 3 1 Engine start 2 Oil level indicator 3 Voltmeter or LED display V voltage Hz frequency T1 current time since the last start T2 total time since the commissioning for KSB 6000DES ATS...

Page 10: ...which is under decompressor lever Pic 5 push the decompressor at the top of cylinder head to reducepressureinthecylinderandreliefextension Vigorouslypullstarterhandleandstarttheengine Do not let a sha...

Page 11: ...tthepositiveterminalofthebattery TurnthemotorsafetyswitchtoONposition SetthekeytoONposition TurnthekeyclockwisetoSTARTposition After the engine launch release the key and it will automatically return...

Page 12: ...ernator to be cooled 3 Incaseofmanualstart settheengineswitchtoOFFposition 4 Incaseofelectricstart turnthekeytoOFFposition 5 For all types of diesel generators there is an emergency stop lever for the...

Page 13: ...ormance of regular maintenance works the manufacturer bears no responsibility for such damages Such damages are also Damages occurred as a result of using non original spare parts Corrosion damages an...

Page 14: ...rformance characteristics and is a major attribute defining its service life Use oils designed for four stroke cycle vehicle engines sincesuchoilscontaincleaningadditives whichcomplyorevenexceed SE st...

Page 15: ...is set on flat level surface 2 Place a drain oil holding tank under the engine 3 Turn the drain cap located under the oil depth gage cap in the engine by means of a 10mm hexagon spanner 4 Wait till th...

Page 16: ...time to time and clean any contaminations Regular air filter maintenance is necessary to maintain sufficient carburetorairinflow Theairfiltershouldbecleanedmoreoftenwhen using generator in dusty condi...

Page 17: ...fueltocleanthefilter 4 Putthefilterbacktothefueltank Thefuelfilterinthefuelsupplypipeline Thisfilterhastobereplacedevery100operatinghours It slocatedunderthefueltank onthefuelhosethroughwhichfuelenter...

Page 18: ...al starter until you feel light resistance so that the intake and exhaust valves are closed Remove the negative terminal of the battery for the electric start models Clean generator from dirt and dust...

Page 19: ...dirty Clean the cooling fins Air filter is dirty Clean the air filter No voltage while engine is working Circuit breaker is active Turn on the circuit breaker Connected cables are corrupted Check the...

Page 20: ...adio 50 250 TV set 100 400 Refrigerator 100 150 Oven 1000 2000 Freezer 100 400 Drill 400 800 Hammer drill 600 1400 Grinding machine 300 1100 Circular saw 750 1600 Electro planer 400 1000 Electro jigsa...

Page 21: ...y installed and connected to the mains supply or misused If the claimed malfunction cannot be diagnosed or demonstrated If proper operation of the product can be restored following cleaning from dust...

Page 22: ......

Page 23: ...CONTACTS Germany ks power de info dimaxgroup de Poland ks power pl info pl dimaxgroup de Ukraine ks power com ua sales ks power com ua...

Reviews: