Kamstrup 66-0F-000-100 Installation Manual Download Page 3

S7210-038 GB/2004-10-19/Rev.C1

3

Type 66-0F-000-100

1.                       General information

The LON module for MULTICAL

®

 makes it possible to integrate the MULTICAL

®

 heat meter in a LON

network via the module's FTT-10 A transciever. This ensures an ideal data transfer to the CTS system, as
the remote registration always corresponds with the local reading.

When the LON module is used together with MULTICAL

®

 type 66-CDE, type 66-MP type 66-ST or

MULTICAL

®

 III type 66-B the actual data for water flow, temperature and power is updated every 60 sec..

Furthermore, a program version with more frequent up-dates is available. Current flow, temperature and
power data is updated every 10 seconds, which means that current heat meter data can be used as
input veriables for regulation. Other data is updated at intervals of 50 secons. This program version is
available at Kamstrups home page. (

www.kamstrup.dk

).

Temperature records and power calculation are updated for every energy integration in MULTICAL

®

(20…600 sec. interval depending on the actual water flow).

Kamstrup makes a complete functional test at the factory, therefore the module is delivered
Configured. Which is why the service LED will be off when voltage is supplied.

Please refer to the EcheLon Engineering Bulletin ”LonWorks Custom Node Development”, which
explains the various indications of the "Service" LED.

Summary of Contents for 66-0F-000-100

Page 1: ...Rev C1 1 LON Module for MULTICAL MULTICAL III Installation Guide Type 66 0F 000 100 Kamstrup A S Industrivej 28 Stilling DK 8660 Skanderborg TEL 45 89 93 10 00 FAX 45 89 93 10 01 E MAIL energi kamstrup dk WEB www kamstrup com ...

Page 2: ... 10 19 Rev C1 2 Contents 1 General information 3 1 1 Detailed information 4 2 Hardware installation 4 2 1 Reset 6 3 MULTICAL I O ports 6 3 1 Pulse inputs 6 3 2 Pulse outputs 7 4 Final assembly 7 LON module for MULTICAL ...

Page 3: ...frequent up dates is available Current flow temperature and power data is updated every 10 seconds which means that current heat meter data can be used as input veriables for regulation Other data is updated at intervals of 50 secons This program version is available at Kamstrups home page www kamstrup dk Temperature records and power calculation are updated for every energy integration in MULTICA...

Page 4: ...MULTICAL III If MULTICAL MULTICAL III is used for billing purposes and is sealed the seals must only be broken as agreed with the local utility which usually is the owner of the meter Furthermore the LON module can be placed in an external communication unit outside MULTICAL MULTICAL III Data transmission between the LON module and MULTICAL MULTICAL III is done via a 3 wire cable connected to a da...

Page 5: ...transformer coupled However in connection with ring topology the same polarity must be used at all connections The transciever of the LON module is of the type FTT 10A Free Topology Transceiver and thus the module can be used in all topologies bus ring star with a total cable length of up to 500 m and a stub length of up to 0 3 m When pure bus topology is used it is possible to use a cable length ...

Page 6: ... ports The LON module is equipped with 2 I O ports which can either be used as pulse inputs or as pulse outputs for MULTICAL MULTICAL III depending on the configuration of the MULTICAL MULTICAL III in question FF and GG coding The LON module automatically reads the configuration in MULTICAL MULTICAL III and the ports are set in the correct direction 3 1 Pulse inputs When MULTICAL MULTICAL III is c...

Page 7: ...ty limiter for heat flow rate and water flow The outputs must never be subject to stress above 10 mA and 30 V When MULTICAL MULTICAL III is used for valve control PQ limiter the Flow Controller type S7590006 must be used Ask for instruction no 5511 764 for further details on installation and commissioning of the PQ limiter 4 Final assembly Mount the calculator top and the two screws on the sides S...