Operating instructions

Connect the meter in accordance with the installation diagram on the meter’s type label.
Depending on the configuration a fixed value will be displayed, or the display will 
change between selected indications every 10 seconds. 
It is possible to change the display reading manually by activating the push button on 
the meter. The available readings will depend on the meter’s configuration.

Security and installation guidelines 

The meter is only to be used for measuring electrical energy and shall operate within the 
specified values only.
The meter must be disconnected when working on it. It can be highly dangerous to touch 
the meter parts when the meter is switched on. 
Therefore, the relevant security fuse must be removed and kept in a place where it cannot 
be inserted by unauthorized persons.
Current local standards, guidelines, regulations and instruction must be observed. Only 
authorized personnel is permitted to install electricity meters. 
Meters for direct connection must be protected against short circuit by a security fuse in 
accordance with the maximum current stated on the meter.

The meter constant LED blinks proportionally to the consumed active energy.
Only authorized personnel must break the utility sealing.

Utility seals

LCD-display

Optical interface

LED (meter constant)

Push button

Type label

LED breaker status 

(only meters with 

internal breaker)