Technical description 

24 

 

DRS30-DRS125 

11.10.4 How is controlled the condenser fan 

DRS 30-100

 A temperature probe BT2 is located on the discharge side of the condenser. The condenser fan is 

activated (ON) when the BT2 temperature is higher than FANon setting (approx. 35°C/96°F) and led 

 is ON.  

Condenser fan stops when BT2 temperatures is lower than FANoff setting (approx. 30°C/86°F). 

 
DRS 125

 A pressure probe BP2 is located on the discharge side of the compressor. The condenser fan is activated 

(ON) when the BP2 pressure is higher than FANon setting (approx. 18 barg/260 psig) and led 

 is ON.  

Condenser fan stops when BP2 pressure is lower than FANoff setting (approx. 14 barg/203 psig). 
 

11.10.5 How is controlled the drain solenoid valve 

Drain solenoid valve is activated (ON) for T

ON

 seconds (standard 2 seconds) every T

OFF

 minutes (standard 1 minute). 

Led 

 shows that condensate drain solenoid valve is ON. 

The condensate drain test is always active using the button 

NOTE :

 if an electronic drainer is installed, DMC35 is set to keep always powered the drain output, Led 

 is 

always OFF and condensate drain test does not work. 
 

11.10.6 How to display the total hours of operation 

Total hours of operation are recorded into DMC35 and are shown through the dew point indication bar (max value 
109900 hours, cannot be reset).  

With dryer ON press buttons 

 and 

 for at least 5 seconds. 

Led 

 is lit and a certain numbers of leds of dew point indication bar are light up. The number of leds lit define the 

1st digit of hour counter (ie : no leds lit 

 1st digit =0) 

Press 

 button, led 

 is lit and a certain numbers of leds of dew point indication bar are light up. The 

number of leds lit define the 2nd digit of hour counter (ie : n.3 leds lit 

 2nd digit = 3) 

Press 

 button, led 

 is lit and a certain numbers of leds of dew point indication bar are light up. The 

number of leds lit define the 3rd digit of hour counter (ie : n.8 leds lit 

 3rd digit = 8) 

Total operating hours : 0 3 8 x 100 (fixed multiplying ratio) = 3800 hours 

Press 

 button repeatedly to scroll the displaying of 3 digits again. 

Press 

 button to exit total hours display (if no button is pressed after 30 seconds the menu is exited 

automatically). 
 

11.10.7 How to change the operating parameters 

– SETUP menu 

The setup menu can be used to change the dryer’s operating parameters. 

 

 

Only qualified personnel must be allowed to access to the setup menu. The manufacturer is not 
responsible for malfunctioning or failure due to modification to the operating parameters. 

With dryer ON press button 

 for at least 2 seconds to enter the setup menu. 

Access to the menu is confirmed by led 

 flashing.  

Keep 

 pressed and use arrows 

 to change the value. Release the button 

 to confirm the value. 

Press shortly 

 to skip to following parameter. 

Press 

 to exit setup menu (if no button is pressed after 2 minutes the menu is exited automatically). 

Display 

Description 

Limits 

Resolution 

Standard 

setup 

Synchronous flashing 

led 

 + led 

 

T

ON

 

– drain time ON : time ON 

condensate drain valve 

1 … 6 sec 

1 sec 

Non-Synchronous flashing 

led 

 + led 

 

T

OFF

 - drain time OFF : pause time 

for condensate drain valve 

1 … 10 min 

1 min 

NOTE :

 parameter values are displayed on the 10 led display where 1st (left) led is the lowest limit and 10th (right) is 

the highest limit. 

 

NOTE (1):

 T

ON

 set at the 10

th

 led (right) keep drain output always powered and led 

 always off (used if electronic 

drainer is installed) 
 

Set

ON

Set

Set

ON

Set

Set

Set

ON

ON

Summary of Contents for DRS30

Page 1: ...Instructions for installation and operation Compressed air refrigeration dryer DRS30 DRS125 EN English...

Page 2: ...Please read these installation and operating instructions carefully before mounting and starting up the DRS30 DRS125 and follow our directions Perfect functioning of the DRS30 DRS125 and thus reliabl...

Page 3: ...Filter dryer 22 11 7 Capillary tube 22 11 8 Aluminium heat exchanger 22 11 9 Hot gas bypass valve 22 11 10 Electronic instrument DMC35 23 11 10 1 How to switch on the dryer 23 11 10 2 How to switch of...

Page 4: ...lectric diagrams 39 13 6 1 Electric diagrams list of components 39 13 6 2 Electric diagram DRS 30 100 40 13 6 3 Electric diagram DRS 125 41 Pos 1 Beko Technische Dokum entati on berschriften 1 Sicherh...

Page 5: ...nnel prior to installation start up and maintenance The operating instructions must be accessible at all times at the place of application of the DRS30 DRS125 compressed air refrigeration dryer In add...

Page 6: ...grounded in the respective provisions and laws and capable of carrying out the required works and of identifying and avoiding any risks during the machine transport installation operation and maintena...

Page 7: ...carefully designed with particular attention paid to environmental protection CFC free refrigerants CFC free insulation material Energy saving design Limited acoustic emissions Dryer and packaging com...

Page 8: ...cident prevention regulations required for the respective case of application need to be observed during employment This applies accordingly when accessories are used Danger Compressed air Risk of ser...

Page 9: ...rigerant carrying parts remove the refrigerant to such an extent that safe working is possible 4 Do not eat drink or smoke during work Keep out of the reach of children 5 Breathing protection ambient...

Page 10: ...83616103770_6 doc 4009os 9 Beko Technische D okumentati on Sicherheit Zusatz Sicher hei tshi nw eise BM 33 0 m od_1231926887620_6 doc 12829s 10 Beko Technische D okumentati on Sicher heit Vorsicht Feh...

Page 11: ...DRS30 DRS125 compressed air refrigeration dryer must neither be installed in insufficiently ventilated rooms nor near heat sources or inflammable substances To avoid fractures resulting from material...

Page 12: ...ting compressor and in a loss of efficiency and performance of the dryer This in turn leads to overheated condenser fan motors to malfunction of electric components and to a breakdown of the dryer Fai...

Page 13: ...throughput rate of the compressor The storage capacity of the tank must be dimensioned in such a way that a possible short term high air demand peak air consumption can be compensated Do not obstruct...

Page 14: ...ient temperature 90 F 32 C Inlet air temperature 110 F 43 C Factor F1 1 00 Factor F2 1 09 Factor F3 0 81 Each item of data has a corresponding numerical factor which multiplied by the design air flow...

Page 15: ...e pipework Ende der St ckliste Note Contaminated intake air In the event that the intake air is strongly contaminated ISO 8573 1 class 3 3 or poorer quality we recommend the additional installation of...

Page 16: ...mpressors dryers tanks filters etc is supplied We recommend an oil water separator for dispersed compressor condensate and an emulsion splitting plant for emulsified condensate 9 Start up 9 1 Prelimin...

Page 17: ...system Ensure that the manual valve of the condensate drainage cycle is open Remove any packaging material and other items which may block the space around the dryer Establish the mains connection pl...

Page 18: ...int temperature indicated on the electronic control unit is stable and whether or not the condensate is drained off at regular intervals Establish the compressed air supply During the operation the re...

Page 19: ...Technical data DRS30 DRS125 19 10 Technical data...

Page 20: ...it is reheated to up to 15 F 8 C below the inlet temperature when leaving the dryer Refrigeration cycle The refrigerant is conducted through the compressor and reaches a condenser under high pressure...

Page 21: ...e separator 12 2 Temperature probe BT2 Fan control 2 Not installed 13 Condensate drain service valve 3 Not installed 14 Condensate drain strainer 4 Not installed 15 Condensate drain solenoid valve 6 C...

Page 22: ...ot required 11 8 Aluminium heat exchanger The heat exchanger module consists of an air air heat exchanger an air refrigerant heat exchanger and of a high performance separator The compressed air flows...

Page 23: ...one or more service warnings alarms are active Led shows that condensate drain solenoid valve is ON Led shows that condenser fan is ON The condensate drain test is always active using the button 11 10...

Page 24: ...oint indication bar are light up The number of leds lit define the 2nd digit of hour counter ie n 3 leds lit 2nd digit 3 Press button led is lit and a certain numbers of leds of dew point indication b...

Page 25: ...are parts and dismantling chapters leads to the expiration of the guarantee Improper maintenance may result in dangerous situations for the personnel and or the device Danger Supply voltage Contact wi...

Page 26: ...lification and expertise of the certified skilled personnel For safe operation the device must only be installed and operated in accordance with the indications in the operating instructions In additi...

Page 27: ...c instrument is faulty replace it There is a leak in the refrigerant circuit contact a refrigeration engineer If the fan still doesn t work replace it DewPoint too high The dryer doesn t start see spe...

Page 28: ...ove and clean it Try to remove the electric connector on the solenoid valve if drain stops verify the electric wiring or the electronic instrument is faulty replace it Water within the line The dryer...

Page 29: ...n case of abnormal operation so avoiding to wait for the spares delivery In case of failure of other parts for example inside the refrigerating circuit the replacement must be worked out by a refriger...

Page 30: ...cal formula MIK GWP R134a HFC CH2FCF3 1000 ppm 1430 R407C HFC R32 125 134a 23 25 52 CHF2CF3 CH2F2 CH2FCF3 1000 ppm 1773 85 12 5 Dismantling the dryer When the dryer is dismantled all parts and operati...

Page 31: ...Appendices DRS30 DRS125 31 13 Appendices 13 1 Dryer dimensions DRS 30 40...

Page 32: ...Appendices 32 DRS30 DRS125 13 2 Dryer dimensions DRS 60 80...

Page 33: ...Appendices DRS30 DRS125 33 13 3 Dryer dimensions DRS 100...

Page 34: ...Appendices 34 DRS30 DRS125 13 4 Dryer dimensions DRS 125...

Page 35: ...ot gas bypass valve 37 Pressure transducer 8 Condenser 51 Front panel 9 Condenser fan 52 Back plate 9 1 Motor 53 Right sidewall 9 2 Blade 54 Left sidewall 9 3 Grid 55 Cover 10 Filter dryer 56 Base pla...

Page 36: ...Appendices 36 DRS30 DRS125 13 5 2 Exploded diagram DRS 30 80...

Page 37: ...Appendices DRS30 DRS125 37 13 5 3 Exploded diagram DRS 100...

Page 38: ...Appendices 38 DRS30 DRS125 13 5 4 Exploded diagram DRS 125...

Page 39: ...f installed DMC35 DMC35 electronic instrument air dryer control BT1 T1 Temperature probe dew point BT2 T2 Temperature probe fan control BP2 P2 Pressure transducer fan control S1 ON OFF switch NT1 Only...

Page 40: ...Appendices 40 DRS30 DRS125 13 6 2 Electric diagram DRS 30 100...

Page 41: ...Appendices DRS30 DRS125 41 13 6 3 Electric diagram DRS 125...

Page 42: ......

Page 43: ......

Page 44: ...Contact Information __________________________________________________________ Kaishan USA LLC 15445 Industrial Park Dr Loxely AL 36551 251 257 0586 www KaishanUSA com 74MD0021C0 EN_00...

Reviews: