Electronic control function
9.1 Abbreviation
T1: Indoor ambient temperature
T2: Coil temperature of indoor heat exchanger middle.
T2B: Coil temperature of indoor heat exchanger outlet(This sensor is located in outdoor unit)
T3: Coil temperature of outdoor heat exchanger
T4: Outdoor ambient temperature
T5: Compressor discharge temperature
Ts: Setting temperature
9.2 Electric control working environment.
9.2.1 Input voltage: 198V~264V.
9.2.2 Input power frequency:50Hz.
9.2.3 Indoor fan normal working amp. is less than 1A.
9.2.4 Outdoor fan. normal working amp. is less than 1.5A.
9.2.5 Four-way valve normal working amp. is less than 1A.
9.3
Outdoor unit’s digital display tube
There is a digital display tube in outdoor PCB.
Digital display tube display function
•
In standby , the LED displays
“- -”
•
In compressor operation, the LED display the running frequency,
•
In defrosting mode, The LED displays “dF” or alternative displays between running frequency and
“dF”(each displays 0.5s)
•
In compressor pre-
heating, The LED displays “PH” or alternative displays between running frequency
and “PH”(each displays 0.5s)
•
During the oil return process, The LED displays “RO” or alternative displays between running
frequency
and “RO”(each displays 0.5s)
•
In low ambient cooling mode, the LED displays “LC” or alternative displays between running
frequency
and “LC”(each displays 0.5s)
•
In forced cooling mode, the LED displays “FC” or alternative displays between running frequency and
“FC”(each displays 0.5s)
•
When PFC module protection occurs three times within 15
minutes, the LED displays “E6” or
alternative displays between running frequency
and “E6”(each displays 0.5s)
•
In protection or malfunction, the LED displays error code or protection code.