HEATING AIR CURTAINS
Line Size
SINGLE PHASE (230V~, MINE LINE:L, N)
THREE PHASES
(400V~ MAIN LINE: A, B, C, N)
HEATER POWER (KW)
3
4
5
6
8
10
12
14
3
4
5
6
8
10
12
14
MAIN LINE (mm
2
)
2.5
4.0
6.0
10
1.5
2.5
4.0
6.0
EARTH LINE (mm
2
)
1.5
2.5
4.0
6.0
0.75
1.5
2.5
4.0
NOTE: forbid overload to operation for a long time!
6. oPerAtion
6.1 Controlled by remote controller
a) Press “ON/OFF” button to turn ON the unit. Main receiver receives the signal with the sound
of “beep” to start working with the green light in cool mode at high speed “H”. Press “ON/OFF”
button again to turn OFF.
b) When the unit is working at the above a. situation, press “COOL” button in the Remote control
-
ler, receiver receives the signal with the sound of “beep” and switch high speed to low speed “L”.
Meanwhile there is a green light display in the receiver. Press “COOL” button again, the unit will
switch low speed to high speed. So when the unit is working at cool mode, press “COOL” button
can switch air curtain working under the cycle of Low or High speed.
c) FOR SINGLE PHASE UNIT:
When the unit is working at the above b. situation, press “HEAT”
in the remote controller, receiver receives the signal with the sound of “beep” and switch cool
item
power