background image

Digital Protector

Voltage – Current
         and 
Frequency control

DP01

-72

Phase Sequence Control

Under Voltage Protection

Unbalanced Voltage  
Protection

Over Frequency 
Protection

Under Frequency 
Protection

TRUE  RMS

Latch Function

V

L1

,

V

L2,

V

L3

V

L12,

V

L23,

V

L13

I

L1,

I

L2,

I

L3

Hz

General:

In three phase systems, it measures RMS values of AC voltages,
currents and system frequency sensitively. Using up direction button 
(Select) phase-neutral voltages and phase-phase voltages monitor 
sequentially.
DP01-72 has many  features. 
Those are;
- Phase Failure

(seq)

- Phase Sequence 

(seq)

- Over Voltage Protection

(o - U)

- Under Voltage Protection

(u - U)

- Voltage Unbalance (asymmetry) Protection

(unb)

- Over Current Protection

(o - C)

- Under Current Protection

(u - C)

- Current Unbalance (asymmetry) Protection

(ubC)

- Over Frequency  Protection

(o - F)

- Under Frequency  Protection

(u - F)

When device is turn on if its adjusted voltages and frequency in its 
interval and if phase sequence is correct relay  switch on.
If any of error occurred ( except phase failure and phase sequence ) 
at the end of adjusted time relay switch off its contact. When system
return normal  values, at the end of time out relay switch on.

L1

L2

L3

Re

< t-1

t-1

Phase Failure:  (u-U)

Before starting system , it controls phase absence then if all phases  
exits Normal LED turn on and relay  contact  switch on. In case of 
missing of any L1,L2,L3 phases , Normal LED turn off  and relay  
switch  off its contact .In this case 

u-U 

warn appears

 

on display.

V

L1

Special Buttons:

L1

L2

L3

V

L2

V

L3

L1

L2

L3

V

L12

L1

L2

L3

V

L23

L1

L2

L3

V

L13

Select: 

(Up direction) 

when pressing continuously, 
screen displays  frequency of 
system. When button release 
device continue to show voltage. 

Reset: 

If error case although disappeared 
then device is not return to normal, 
latch-function occurred and it 
makes locked device. 
Or Lock-function (only for currents) 
may be occured.
After checking error in system then 
 restart device with pushing reset 
button.

IMPORTANT:

  L1 - N  is device supply inputs. Thus,the applied L1 – N 

voltage must be rated voltage of  system . Otherwise normal led makes 
flash and the device switched off its output contact.
The measured frequency also  must the  frequency  of the system.

Voltage Unbalanced:  (unb)

The phase-phase voltage unbalance limit can be adjusted  
between(5% - 20%) . When it exceeds the adjusted limit , the device 
switched off its out contact at the end of  t-1 delay. In this case  

unb

 

warn  appears on the screen. For the returning normal state, 
asymmetry values should under  20% (hysteresis value). In this case 
at the end of t3 time Normal LED turned on and output contact switch 
on. If the phase-phase voltage  unbalance, return adjusted value 
shorter than  t-1 time, output relay does not release its contact. 
Hysteresis is 20 %.

unb

 = 000(oFF) protection is disable .

Example:

 Let's say that asymmetry value is set to %15 for a 

3 x 380VAC. 
In this case, relay contact switch off  at (380-(380x0.15))=323 V.
Switch on the contact is performed at 323+(380x%15x%20)= 334V. 
(%20 is the hysteresis).

Re

L1,L2,L3

L2,L3

L1
L2
L3

Phase Sequetion:  (Seq)

In case of wrong phase order , Normal LED turned off and relay 
contact is not switch  on. In this case 

seq

  warn appears on the 

screen. If  phase order is corrected , Normal LED turned on and out 
relay switch on.

hys

+ % unb

V

nom

hys

Level

Re

- % unb

t-1

< t-1

t-1

L1,L3,L2

L1,L2,L3

r-t

r-t

Over Voltage Protection

Under Current Protection

Unbalanced Current  
Protection

Over Current Protection

L1

L2

L3

L1

L2

L3

Display Functions:

    (V

max 

- V

min

 % unb  =

            x 100      Hys = 380 x (% Asm) x (% 20)

         380

AREAS OF OPERATION:
 

■  In-Elevator motors protection
■  On-pump and electric motor 
■  Resistance in oven with

®

Reviews: