3.0 TL3
4.0 TL3
5.0 TL3
6.5 TL3
7.5 TL3
8.6 TL3
9.0 TL3
10.0 TL3
Initial short-circuit alternating
current (Ik" first single period
effective value)
16.5 A
18.9 A
16.5 A
18.9 A
Short circuit current continu-
ous [ms] (max output fault cur-
rent)
1.3 A
Inrush current
1.033 A [RMS (20ms)]
Rated frequency
50/60 Hz
Frequency range
45 - 65 Hz
Reactive power
0 - 95% Snom
cos phi
0.3 - 1 ind/cap
Number of feed-in phases
3
Distortion factor (THD)
0.36 %
0.32 %
0.31 %
0.29 %
3.85 %
0.27 %
Max. voltage range (up to 100
s)
287.5 V / 500 V
AC overvoltage protection
no
4.2
General Data
3.0 TL3
4.0 TL3
5.0 TL3
6.5 TL3
7.5 TL3
8.6 TL3
9.0 TL3
10.0 TL3
General electrical data
Max. efficiency
98.1 %
98.2 %
98.3 %
98.5 %
European efficiency
96.6 %
97.1 %
97.4 %
97.6 %
97.7 %
97.9 %
98.3 %
Self consumption: Standby
3 W
Feed-in from
20 W
Transformer unit
no
Protection class / over voltage
category
I / III (AC) II (DC)
Grid monitoring
Country-specific
Distribution system
TN-C-System, TN-C-S-System, TN-S-System, TT-System
3.0 TL3
4.0 TL3
5.0 TL3
6.5 TL3
7.5 TL3
8.6 TL3
9.0 TL3
10.0 TL3
General Data
Display
Graphical d LEDs
Controls
4-way 2 buttons
Menu languages
DE; EN; FR; IT; ES; PL; NL; PT; CZ; HU; SL; TR; RO
Interfaces
Standard: 2 x Ethernet, USB, RS485, optional: S0, 4-DI, 4-DO
Communication
TCP/IP, Modbus TCP, Sunspec
Potential-free relay
Potential-free NO contact, max. 30 V/1 A DC
DC isolator switch
yes
AC isolator switch
no
Cooling
Fan
Number of fans
1
Noise emission
<53 db(A)
Housing material
Aluminium / plastic
HxWxD
522 mm x 363 mm x 246 mm
Weight
30 kg
Manual
Technical data | 4
KACO blueplanet 3.0 TL3 KACO blueplanet 4.0 TL3 KACO blueplanet 5.0 TL3 KACO blueplanet 6.5 TL3 KACO
blueplanet 7.5 TL3 KACO blueplanet 8.6 TL3 KACO blueplanet 9.0 TL3 KACO blueplanet 10.0 TL3
Page 13
EN
KACO blueplanet
KACO blueplanet
KACO blueplanet