Country-
spec. Set-
tings
Level Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Reconnection condi-
tions
NOTE: Precise switch-on conditions should be specified relat-
ive to the grid conditions.
Min. switch-on voltage
after grid monitoring
10 – 110 [% Unom] /
&
Max. switch-on voltage
after grid monitoring
90 – 126.6 [% Unom]
F
Specify switch-on voltage range after grid error.
Min. switch-on fre-
quency after grid mon-
itoring.
45 – 65 [Hz] / &
Max. switch-on fre-
quency after grid mon-
itoring.
45 – 65 [Hz]
F
Specify switch-on frequency range after grid error.
Min. switch-on voltage
after grid error
10 – 110 [% Unom] /
&
Max. switch-on voltage
after grid error
90 – 126.6 [% Unom]
F
Specify switch-on voltage range after grid error
Min. switch-on fre-
quency after grid error
45 – 65 [Hz] / &
Max. switch-on fre-
quency after grid error
45 – 65 [Hz]
F
Specify switch-on frequency range after grid error.
Grid voltage monitor-
ing
1 - 1800 [s]
&
PV voltage monitoring
1 - 1800000 [ms]
F
Specify the time for monitoring the grid voltage and PV voltage.
Waiting time after grid
error
1 - 1800 [s]
Password protection
Status
1. Set waiting time after grid error.
2. Activate optional password protection.
3. Confirm the action field.
4
1
2
3
4
Shutdown settings
NOTE: Activate shutdown according to generic parameters,
frequency or voltage.
Manual
Configuration and operation | 9
KACO blueplanet gridsave 92.0 TL3
Page 41
EN