1.7 Machine setup menu
Page 44
Docu-No.: 0590020601-EN Rev. 1.6.0
1.7.11
Service sub-menu
Parameter
Definition
S.VAR
Service Variable Function
Display of the service variable name.
See list in the appendix see section
.
S.VAR VALUE
Service Variable Value
Display and change of the service program value as selected with S.
VAR.
TRACETICK
Tracetick
This parameter sets the time interval for recording operating data to
KCM internal memory so that it can be retrieved and viewed on a PC
for later analysis.
Two types of data are recorded: Trace data e.g. massflow and
operational status. e.g. gravimetric control. The second data type
recorded is Alarm History data.
Selections:
Stop: The trace recording is stopped and the data can be read from
the Configuration serial data port using HyperTerminal. When
<Stop> is selected, the data can be read from the KCM at any time
as long as power to the KCM is not interrupted.
Restarting of the <TRACETICK> can be done without losing data if
done within 1 hour of stopping the trace.
1 sample: Each sample point of data is recorded. No more than five
minutes of data can be stored without older data being over-written.
1/4 second: 4 samples per second of data
1 second: 1 sample per second of data
5 seconds: 1 sample of data very 5 seconds
15 seconds: 1 sample of data very 15 seconds
60 seconds: 1 sample of data very 60 seconds
Default: 1 second
Notes:
• The default value of 1 second will return after a KCM power
interruption. Any other value of <Trace Tick> is not stored during
a power interruption.
• There are 3600 individual samples of data in storage. So for a 1
second timetick, 1 hour of data is preserved. For a 60 second
timetick, 60 hours of data are stored.
• Please see manual 0690020601 for operational details on using
this resource.