2 a) Electrical: Electrical work must be performed by a qualified Electrician 

and comply with the  Canadian Electrical Code or the American National 
Standard Electrical Code lnforce.

Table 02.

The wire sizes to be used are as follows:

For installation see Wiring Schematic figure 03.

FIGURE 03.

Wiring Schematic

In Accordance with The Electrical Code in effect

b)

A green coloured terminal (or a wire connector marked “C”,“GP”. “Ground”
or “Grounding”) is provided within the control box. To reduce the risk 
of electric shock, connect this terminal or connector to the grounding 
terminal of the electric service or supply panel with a continuous green 
insulated copper wire equivalent in size to the circuit  conductors

4

Model

Amps

Fuse

(240V G.F.L. Size)

Wire Size

(90’ Copper Only)

Collector

Ground Wire

(Copper Only)

K-5 & KS-5

21A

30A

10

10

K-10 & KS-10

42A

60A

6

6

K-15

63A

80/100A

Use Supply conductor

suitable for 75º C

Use Supply conductor

suitable for 75ºC

3

MECHANICAL INSTALLATION DIAGRAM

SHOWING BY PASS

Caution:

i) Do not store chlorine near or in the same room as heater.

ii) Valves must not be installed in the piping on the 

outlet of heater to the pool.

iii) Use PVC cement for connecting leakage current collectors 

into tank body and use teflon tape as sealer in the threads 
for drain plug.

d) 

Water Flow

The water flow in GPM should not exceed the following limits:

Table 01

Important:

Systems with higher GPM ratings will require a bypass around Heater.
This would be necessary if a high velocity pump is employed in the system.

Recommended:

Add water softener for longer heater life.

Heater

GPM

K-5 / KS-5

08 (Max)

K-10 / KS-10

10

K-15

10

Summary of Contents for K-5

Page 1: ...insulated from the unit The installation of the collectors shall be such that all water entering and leaving the unit flows through the two collectors as shown in Figure 01 The length of the leakage current collectors shall be made of a corrosion resistant metal and shall be provided with a copper lug brazed to the collector body Hand tighten only Do not use high force with a pipe wrench FIGURE 01...

Page 2: ...del Amps Fuse 240V G F L Size Wire Size 90 Copper Only Collector Ground Wire Copper Only K 5 KS 5 21A 30A 10 10 K 10 KS 10 42A 60A 6 6 K 15 63A 80 100A Use Supply conductor suitable for 75º C Use Supply conductor suitable for 75ºC 3 MECHANICAL INSTALLATION DIAGRAM SHOWING BY PASS Caution i Do not store chlorine near or in the same room as heater ii Valves must not be installed in the piping on the...

Page 3: ...n of moisture or water into electrical components At all times the unit must be properly ventilated to avoid condensation FIGURE 05 WIRING DIAGRAMS below 5 supplying this equipment Addition bonding lugs are provided and marks Bonding Lugs To reduce the risk of electric shock connect the bonding lugs in accordance with the Canadian Electric Code Part 1 c It is mandatory that all Electrical Pool hea...

Page 4: ...onnection reconnection charges The above warranty shall be considered void if i The installation instructions are not followed ii Unit is powered without any water circulation iii The power is disconnected and unit is not thoroughly drained at the time of winterizing iv The Unit has been mishandled Warranty Registration must be done within ten days of the purchase of the unit by mailing warranty c...

Reviews: