K-Line KL 20030 NAV Operating Instructions Manual Download Page 7

7

2.   Line the tool up with the proper holes in the cooler as shown.  Hand tighten the 

appropriate knurled screw for the cooler down into the threaded hole until the tool 
contacts the surface.  

3.   Hand tighten the knurled knobs on the tool in order to compress the o-rings and seal 

against the inside of the pipes.  Do not over tighten the knobs as damage to the o-rings 
could result.

KL20030-4:

1.  Thread the plugs into the ports and hand tighten until the o-rings contact the sealing 

surface.  Do not over tighten the plugs as damage to the o-rings could result.

KL20020-13 (P

RESSURE

 R

EGULATOR

):

1.  Connect a pressurized air line to the regulator assembly, and verify that the air pressure 

is being properly regulated to 55 psi.  If it is not, use the regulator’s adjustment knob to 
adjust the pressure to 55 psi.

P

RESSURIZE

 

THE

 S

YSTEM

 

AND

 C

ONDUCT

 T

EST

 #2

IMPORTANT:

 Begin by turning the 3-way valve on tool KL20030-1 to Test 2 (Hose).  This is 

necessary for this part of the test to be completed properly.  Not completing this 
would result in an invalid test and would provide false results.

NOTE:

  The air poppet in KL20030-2 is set to 60 PSI to prevent damage to the coolers 

and for safety in the case of over pressurization.  

The compressed air line that is 

connected to this system must be regulated to 55 PSI.

1.  Connect the KL20020-13 Pressure Regulator to the KL20030-2.  

DO NOT INSTALL ONTO 

THE KL20030-1.  

2.  Check for leaks by placing the end of the hose from the KL20030-1 into a container of 

water to a depth of .375” which is marked with red dye on the hose.  The system must 
remain pressurized and the operator should look for air bubbles to come from the end 
of the hose.  The bubbles indicate a leak, and a very small leak may take up to 

5 minutes 

to appear.  This is the maximum time that would be required of the operator to watch 
for air bubbles to be sure there are no leaks in the cooler.  

NOTE:

  Be sure to record if the EGR coolers passed or failed the leak test.

D

ISASSEMBLY

 

1.  Disconnect the compressed air line from the system.

2.  Remove all tools from coolers and clean any oil and dirt from them.  Refer to installation 

instructions and reverse them for removal.

3.  Replace the tools in the storage case for protection.

Summary of Contents for KL 20030 NAV

Page 1: ...KL 20030 NAV EGR LEAK DETECTION KIT 2010 MAXXFORCE DT 9 10 OPERATING INSTRUCTIONS ...

Page 2: ...rator must be familiar with vehicle cooling systems coolants and the dangers they present If the operator cannot read English operating instructions and safety precautions must be read and discussed in the operator s native language Si el operador no puede leer inglés las instrucciones de operación y las precauciones de seguridad deberán leerse y comentarse en el idioma nativo del operador Si l ut...

Page 3: ...econd test uses air pressure while the operator looks for leaks in the form of bubbles in a can of water to check for leaks in the coolant side of the EGR Cooler system APPLICATION 2010 MaxxForce DT 9 10 CONTENTS PART DESCRIPTION QTY KL20030 1 Leak Detection Plate 1 KL20030 2 Double Hole Seal 1 KL20030 3 Gooseneck End Seal 1 KL20030 4 Sealing Plug 2 KL20030 1 Leak Detection Plate KL20030 2 Double ...

Page 4: ...the Pressure Regulator KL20020 13 to 55 psi before connecting it to the system and beginning the test NOTE Always conduct the two EGR Cooler tests in the order shown Completing the tests in a backwards order could give faulty results INSTALL TOOLS TEST 1 The EGR Cooler shown below with required tools installed to complete Test 1 KL20030 1 1 Place the tool on the lange aligning the knurled knobs wi...

Page 5: ... TEST 1 NOTE The air poppet in KL20030 3 is set to 60 PSI to prevent damage to the coolers and for safety in the case of over pressurization The compressed air line that is connected to this system must be regulated to 55 PSI 1 Begin with the 3 way valve on the KL20030 1 at Test 1 Position 2 Closed Connect the KL20020 13 Pressure Regulator to the air inlet on the KL20030 1 atTest 1 Position 1 Air ...

Page 6: ...ll the tool onto the pipe as shown Make sure the quick connect is fully seated and locked onto the pipe before hand tightening the knurled knob 3 When the quick connect is fully seated the knurled knob can be hand tightened until the rubber seal contacts the pipe Do not over tighten the knob as damage to the o ring and the pipe could result KL20030 2 1 Before installing the tool back the knurled k...

Page 7: ...g this would result in an invalid test and would provide false results NOTE The air poppet in KL20030 2 is set to 60 PSI to prevent damage to the coolers and for safety in the case of over pressurization The compressed air line that is connected to this system must be regulated to 55 PSI 1 Connect the KL20020 13 Pressure Regulator to the KL20030 2 DO NOT INSTALL ONTO THE KL20030 1 2 Check for leak...

Page 8: ...ries Inc P N 4420030 200 Rev 8 11 For product information or to purchase replacement parts CALL CUSTOMER SERVICE AT 1 800 824 K LINE 5546 Local 616 396 3564 FAX 1 800 528 9138 or 616 396 8974 cservice klineind com www klineind com ...

Reviews: