1. INTENDED USE
TROPIC heating units, size 1 and 2, are intended to heat such compartment as:
»
shopping centres;
»
fashion houses;
»
churches;
»
sports and entertainment facilities;
»
car showrooms.
As well as in places where traditional heating units are used, i.e. in warehouses, factory halls,
workshops, greenhouses, etc.
The units cannot be used in the compartments with relative humidity larger than 90%
and air dust concentration over 3mg/m
3
.
The compartment can be served by one or larger number of the units, also by the units of different
sizes.
2. DESIGNATIONS
Heating unit
TROPIC- 1 -II
Size
1; 2
Number of heater rows
I; II
3. DEVICE DESCRIPTION
The units are adapted to operate in the horizontal position as ceiling units and in the vertical position
as wall units.
The heaters of the units are designed in such a way that they are completely vented both operating
in the horizontal and vertical position.
The unit includes:
»
axial fan mounted on the rear wall of the unit with a net protecting the rotor.
»
(I or II row) fin water heater in the frame made of galvanized steel sheet.
»
casing made of high quality plastic with a single-row outlet grid allowing adjusting a direction
of supplied air. The structure of grid blades protects against an automatic rearrangement of the
blades.
The fin heater is made of copper pipes with external diameter D=12mm and aluminium fins with
spacing s=2,4mm.
The connection spouts of the units have external threads.
For the fin water heaters the maximum temperature of heating medium is up to 150
O
C
and the maximum operational pressure is up to 1,5Mpa.
There is a risk of heating medium freeze in the heater in the compartments with
the temperature below 0
O
C.
The risk can be reduced using an antifreeze thermostat (delivered at request), using antifreeze
heating media or removing water from the unit.