![Juro-Pro Eco II 16L Instruction Manual Download Page 24](http://html1.mh-extra.com/html/juro-pro/eco-ii-16l/eco-ii-16l_instruction-manual_2034191024.webp)
22
refrigerants are recovered safely. Prior to the task being carried out, an oil and
refrigerant sample shall be taken in case analysis is required prior to re-use of
reclaimed refrigerant. It is essential that electrical power is available before the task is
commenced.
1)
Become familiar with the equipment and its operation.
2)
Isolate system electrically.
3)
Before attempting the procedure ensure that:
a)
Mechanical handling equipment is available, if required, for handling refrigerant
cylinders.
b)
All personal protective equipment is available and being used correctly.
c)
The recovery process is supervised at all times by a competent person.
d)
Recovery equipment and cylinders conform to the appropriate standards.
4)
Pump down refrigerant system, if possible.
5)
If a vacuum is not possible, make a manifold so that refrigerant can be removed
from various parts of the system.
6)
Make sure that cylinder is situated on the scales before recovery takes place.
7)
Start the recovery machine and operate in accordance with manufacturer's
instructions.
8)
Do not overfill cylinders. (No more than 80 % volume liquid charge).
9)
Do not exceed the maximum working pressure of the cylinder, even temporarily.
10) When the cylinders have been filled correctly and the process completed, make
sure that the cylinders and the equipment are removed from site promptly and all
isolation valves on the equipment are closed off.
11) Recovered refrigerant shall not be charged into another refrigeration system
unless it has been cleaned and checked.
10. Labeling
Equipment shall be labeled stating that it has been de-commissioned and emptied of
refrigerant. The label shall be dated and signed. Ensure that there are labels on the
equipment stating the equipment contains flammable refrigerant.
11. Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it
is recommended good practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant