Power cable or cables appropriate for your geographical location available to connect
DC power to the TCX1000-RDM20.
NOTE:
Each power supply must be connected to a dedicated power source
outlet. We recommend connecting each power supply to a different power
source for redundancy purposes.
To connect DC power to a TCX1000-RDM20:
1.
Prevent ESD damage to your equipment by attaching an ESD grounding strap to your
bare wrist, and then connecting the strap to an approved site ESD grounding point.
2.
Ensure that the power supplies are fully inserted in the chassis and the latches are
secure.
3.
Ensure that the power source is turned off, the voltage across the DC power source
cable leads is 0 V, and there is no chance that the cable leads might become active
during installation.
4.
Remove the plastic cover from the terminal block on the power supply. Remove the
terminal block screws.
5.
Identify the positive and negative feed positions, as marked on the power supply.
6.
Strip each of the wires coming out from the DC-input power source by 8-9 mm. Do
not strip more than required, because doing so can leave the wire exposed from the
DC connector after installation. The cable must be terminated with the supplied ring
lug (Panduit PN14-8R-C).
7.
Insert the lug into the terminal block. See
.
Figure 7: Attaching the Lug and Cable
Copyright © 2018, Juniper Networks, Inc.
10
TCX1000 Programmable ROADM Quick Start Guide