Figure 15: Power Distribution from DC and High-Capacity AC Power Supplies in the SRX5800 Services
Gateway Chassis
Zone 0
Zone 1
PEM0
PEM1
PEM2 PEM3
g030291
NOTE:
The craft interface draws its power from the SCBs installed in the SCB slots 0, 1, and 2
at the center of the card cage. In the standard configuration, with SCBs in slots 0 and 1, the craft
interface is powered on even when one of the two zones loses power. But if the chassis only
has one SCB installed, the craft interface draws all of its power from that card, and consequently
is powered off if the zone in which that SCB is installed loses power.
You can install either two or four DC power supplies or high-capacity AC power supplies. Two power
supplies are required to power the two zones, while four power supplies provide full redundancy for both
zones. The power supplies in slots PEM0 and PEM2 form a redundant pair, as do the power supplies in
slots PEM1 and PEM3. When two power supplies are installed for a zone, they share the load. If a power
supply fails, its redundant power supply assumes the full load of that zone without interruption.
If you do install only two power supplies, they must be installed so that one is in an odd-numbered slot
and the other is in an even-numbered slot. For example, you can install one high-capacity AC power supply
in each of the slots PEM0 and PEM1.
SRX5800 Services Gateway Standard-Capacity AC Power Supply
Each standard-capacity AC power supply has a corresponding AC appliance inlet located in the chassis
directly above the power supply. Each inlet requires a dedicated AC power feed and a dedicated
15 A (250 VAC) circuit breaker. See
.
49
Summary of Contents for SRX 5800
Page 1: ...SRX5800 Services Gateway Hardware Guide Published 2020 02 10 ...
Page 23: ......
Page 30: ...Figure 2 Rear View of a Fully Configured AC Powered Services Gateway Chassis 31 ...
Page 111: ...LEDs 112 ...
Page 121: ...Port and Interface Numbering 122 ...
Page 127: ...Port and Interface Numbering 128 ...
Page 161: ......
Page 179: ... One SRX5K MPC IOC2 Modular Port Concentrator with two Modular Interface Cards MICs 180 ...
Page 180: ... One SRX5K 40GE SFP I O card IOC 181 ...
Page 205: ......
Page 261: ......
Page 324: ...c Upload the configuration to RE2 from the USB device 325 ...
Page 365: ...Figure 143 Installing an SPC 366 ...
Page 367: ...368 ...
Page 422: ...5 CHAPTER Troubleshooting Hardware Troubleshooting the SRX5800 425 ...
Page 423: ......
Page 457: ......
Page 473: ...475 ...
Page 476: ...Restricted Access Area Warning 478 ...
Page 483: ...485 ...
Page 496: ...Jewelry Removal Warning 498 ...
Page 499: ...Operating Temperature Warning 501 ...
Page 509: ...DC Power Disconnection Warning 511 ...
Page 513: ...DC Power Wiring Sequence Warning 515 ...
Page 516: ...DC Power Wiring Terminations Warning 518 ...
Page 519: ...DC Power Disconnection Warning 521 ...
Page 523: ...DC Power Wiring Sequence Warning 525 ...