SRX5800 Services Gateway Power System Overview
The SRX5800 Services Gateway uses either AC or DC power supplies. The services gateway is configurable
with two to four AC power supplies or two or four DC power supplies. The power supplies connect to the
midplane, which distributes the different output voltages produced by the power supplies to the services
gateway components, depending on their voltage requirements.
describes the different types of power supplies available.
Table 12: Power Supply Type Summary
Power
Distribution
Redundancy
Maximum Output
Input Condition (If Any)
Power Supply Type
Shared
3+1
1700 W
AC standard-capacity
Zoned
2+2
1700 W
One AC input
AC high-capacity
4100 W
Two AC inputs
1700 W
DC standard-capacity
1700 W
One DC input
DC high-capacity
4100 W
Two DC inputs
NOTE:
The services gateway must be running Junos OS Release 10.4 or later in order to use
high-capacity AC power supplies. The services gateway must be running Junos OS Release
12.1X44-D10 or later in order to use high-capacity DC power supplies.
Redundant power supplies are hot-removable and hot-insertable. Each power supply is cooled by its own
internal cooling system.
NOTE:
Devices configured from the factory with DC power supplies are shipped with a blank
panel installed over the power distribution modules. Devices configured with AC power supplies
have no blank panel.
47
Summary of Contents for SRX 5800
Page 1: ...SRX5800 Services Gateway Hardware Guide Published 2020 02 10 ...
Page 23: ......
Page 30: ...Figure 2 Rear View of a Fully Configured AC Powered Services Gateway Chassis 31 ...
Page 111: ...LEDs 112 ...
Page 121: ...Port and Interface Numbering 122 ...
Page 127: ...Port and Interface Numbering 128 ...
Page 161: ......
Page 179: ... One SRX5K MPC IOC2 Modular Port Concentrator with two Modular Interface Cards MICs 180 ...
Page 180: ... One SRX5K 40GE SFP I O card IOC 181 ...
Page 205: ......
Page 261: ......
Page 324: ...c Upload the configuration to RE2 from the USB device 325 ...
Page 365: ...Figure 143 Installing an SPC 366 ...
Page 367: ...368 ...
Page 422: ...5 CHAPTER Troubleshooting Hardware Troubleshooting the SRX5800 425 ...
Page 423: ......
Page 457: ......
Page 473: ...475 ...
Page 476: ...Restricted Access Area Warning 478 ...
Page 483: ...485 ...
Page 496: ...Jewelry Removal Warning 498 ...
Page 499: ...Operating Temperature Warning 501 ...
Page 509: ...DC Power Disconnection Warning 511 ...
Page 513: ...DC Power Wiring Sequence Warning 515 ...
Page 516: ...DC Power Wiring Terminations Warning 518 ...
Page 519: ...DC Power Disconnection Warning 521 ...
Page 523: ...DC Power Wiring Sequence Warning 525 ...