user@host>
show chassis alarms
NOTE:
If the SRX5800 chassis has redundant power supply modules, and if one PSM
fails, the card can still be online. Only the No redundant power supply alarm is raised.
If the SRX5800 chassis does not have redundant power supply modules, failure of one
PSM can cause the cards to go offline, depending on the total chassis power available at
that time.
3. When the power consumption of a card is more than the allocated budget for 60 seconds, PWR Range
Overshoot alarm is raised for that particular card.
user@host>
show chassis alarms
Calculating Power Requirements to Support Eight SRX5K-SPC3s with Three
IOC3s or Three IOC4s on an SRX5800 Services Gateway
Ambient temperature is the maximum operating temperature for a device. By configuring an ambient
temperature on SRX5800 Services Gateway, you can optimize power provisioned for SPC3, IOC3 and
IOC4 on SRX5800.
After you set the ambient temperature of SRX5800 to 25° C, SRX5800 can support eight SRX5K-SPC3s
with three IOC3s or three IOC4s.
The SRX5800 Services Gateway chassis with normal-capacity AC power supplies has one overall zone.
The SRX5800 Services Gateway Chassis with high-capacity AC power supplies or either standard- or
high-capacity DC power supplies is zoned. Zoning means that certain components are powered by specific
power supplies (see
and
for information on zoning). When
calculating power requirements, be sure that there is adequate power for each zone.
Three AC power supplies are mandatory for a SRX5800 Services Gateway chassis with normal-capacity
AC power supplies.
173
Summary of Contents for SRX 5800
Page 1: ...SRX5800 Services Gateway Hardware Guide Published 2020 02 10 ...
Page 23: ......
Page 30: ...Figure 2 Rear View of a Fully Configured AC Powered Services Gateway Chassis 31 ...
Page 111: ...LEDs 112 ...
Page 121: ...Port and Interface Numbering 122 ...
Page 127: ...Port and Interface Numbering 128 ...
Page 161: ......
Page 179: ... One SRX5K MPC IOC2 Modular Port Concentrator with two Modular Interface Cards MICs 180 ...
Page 180: ... One SRX5K 40GE SFP I O card IOC 181 ...
Page 205: ......
Page 261: ......
Page 324: ...c Upload the configuration to RE2 from the USB device 325 ...
Page 365: ...Figure 143 Installing an SPC 366 ...
Page 367: ...368 ...
Page 422: ...5 CHAPTER Troubleshooting Hardware Troubleshooting the SRX5800 425 ...
Page 423: ......
Page 457: ......
Page 473: ...475 ...
Page 476: ...Restricted Access Area Warning 478 ...
Page 483: ...485 ...
Page 496: ...Jewelry Removal Warning 498 ...
Page 499: ...Operating Temperature Warning 501 ...
Page 509: ...DC Power Disconnection Warning 511 ...
Page 513: ...DC Power Wiring Sequence Warning 515 ...
Page 516: ...DC Power Wiring Terminations Warning 518 ...
Page 519: ...DC Power Disconnection Warning 521 ...
Page 523: ...DC Power Wiring Sequence Warning 525 ...