Table 78: Mounting Hole Locations for Installing the Four-Post Mounting Shelf (continued)
Distance Above U Division
Hole
0.86 U
1.50 in. (3.8 cm)
3
0.50 U
0.88 in. (2.2 cm)
2
0.14 U
0.25 in. (0.6 cm)
1
Table 79: Mounting Hole Locations for Installing a MX2010 Chassis in a Four-Post Rack or Cabinet
Distance Above U Division
Hole
36.50 U
63.88 in. (162.2 cm)
110
33.50 U
58.63 in. (148.9 cm)
101
30.50 U
53.38 in. (135.6 cm)
92
27.50 U
48.13 in. (122.2 cm)
83
24.50 U
42.88 in. (108.9 cm)
74
21.50 U
37.63 in. (95.6 cm)
65
18.50 U
32.38 in. (82.2 cm)
56
15.50 U
27.13 in. (68.9 cm)
47
12.50 U
21.88 in. (55.6 cm)
38
9.50 U
16.63 in. (42.2 cm)
29
6.50 U
11.38 in. (28.9 cm)
20
3.50 U
6.13 in. (15.6 cm)
11
The holes in the front-mounting flanges are spaced at 3 U (5.25 in. (13.3 cm).
SEE ALSO
Verifying the MX2010 Parts Received | 226
234
Summary of Contents for MX2010
Page 1: ...MX2010 Universal Routing Platform Hardware Guide Published 2019 12 03...
Page 28: ......
Page 30: ...MX2010 Power System Description 95 MX2010 Cooling System Description 45 4...
Page 144: ...MX2010 DC Power 48 V System Electrical Specifications 201 122...
Page 146: ......
Page 233: ......
Page 273: ...Figure 98 Loading the MX2010 Router into the Rack g007436 256...
Page 294: ...Figure 113 Reinstalling an AC Power Distribution Module g007440 D 277...
Page 295: ...Figure 114 Reinstalling a DC Power Distribution Module 48 V D g007432 278...
Page 373: ...4 PART Installing and Replacing Components Installing Components 359 Replacing Components 429...
Page 374: ......
Page 620: ......
Page 715: ...6 PART Troubleshooting Hardware Troubleshooting Components 703...
Page 716: ......
Page 744: ......
Page 772: ......
Page 775: ...763...
Page 783: ...772...
Page 796: ...Jewelry Removal Warning 787...
Page 799: ...Operating Temperature Warning 790...
Page 808: ...DC Power Disconnection Warning 799...
Page 812: ...DC Power Wiring Sequence Warning 803...