Figure 76: 6-AWG DC Power Cable Lug
g007468
0.63 ±.02
.27 ±.02
2 PLC
.48 ±.04
End view
Inner diameter .22
.25 ±.04
All measurements in inches
CAUTION:
Before router installation begins, a licensed electrician must attach a cable
lug to the grounding and power cables that you supply. A cable with an incorrectly
attached lug can damage the router.
CAUTION:
The router is a pluggable type A equipment installed in restricted access
location. It has a separate protective earthing terminal (Metric [–M6] and English
[–¼-20] screw ground lugs) provided on the chassis in addition to the grounding pin
of the power supply cord. This separate protective earth terminal must be permanently
connected to earth.
summarizes the specifications for the DC power cables, which you must supply.
Table 75: DC Power Cable Specifications
Quantity and Specification
Cable Type
Eighteen pairs of 4-AWG (21.2 mm
2
), used with 80-A PDM. Minimum
90°C wire, or as required by the local code.
Power
Eighteen pairs of 6-AWG (13.3 mm
2
), used with 80-A PDM. Minimum
90°C wire, or as required by the local code.
CAUTION:
You must ensure that power connections maintain the proper polarity.
The power source cables might be labeled (+) and (–) to indicate their polarity. There
is no standard color coding for DC power cables. The color coding used by the external
DC power source at your site determines the color coding for the leads on the power
cables that attach to the terminal studs on each PDM.
210
Summary of Contents for MX2010
Page 1: ...MX2010 Universal Routing Platform Hardware Guide Published 2019 12 03...
Page 28: ......
Page 30: ...MX2010 Power System Description 95 MX2010 Cooling System Description 45 4...
Page 144: ...MX2010 DC Power 48 V System Electrical Specifications 201 122...
Page 146: ......
Page 233: ......
Page 273: ...Figure 98 Loading the MX2010 Router into the Rack g007436 256...
Page 294: ...Figure 113 Reinstalling an AC Power Distribution Module g007440 D 277...
Page 295: ...Figure 114 Reinstalling a DC Power Distribution Module 48 V D g007432 278...
Page 373: ...4 PART Installing and Replacing Components Installing Components 359 Replacing Components 429...
Page 374: ......
Page 620: ......
Page 715: ...6 PART Troubleshooting Hardware Troubleshooting Components 703...
Page 716: ......
Page 744: ......
Page 772: ......
Page 775: ...763...
Page 783: ...772...
Page 796: ...Jewelry Removal Warning 787...
Page 799: ...Operating Temperature Warning 790...
Page 808: ...DC Power Disconnection Warning 799...
Page 812: ...DC Power Wiring Sequence Warning 803...