Figure 75: Installing an AC Power Supply in an MX10016
g050731
Keep latch in open position during installation.
12. Attach each power cord to a dedicated AC power source outlet.
13. Squeeze the two sides of the power cord retainer clip and insert the ends of the clip into the holes in
the bracket on each side of the AC appliance inlets on the AC power supply faceplate. See
.
14. Locate two power cords shipped with the router; the cords have plugs appropriate for your geographical
location.
15. Insert the power cord coupler into the power supply.
Each AC power supply has two independent 16 A rated AC inlets on the faceplate. Each inlet must be
connected to a dedicated AC power feed to achieve 2N source redundancy. If redundancy is not a
requirement, use the default input INP1 for a single connection.
16. Fasten the cord retainer by lowering the clip over the cord and pushing the cord into the adjustment
nut of the cord retainer. Rotate the nut until it is tight against the base of the cord. See
.
178
Summary of Contents for MX10016
Page 1: ...MX10016 Universal Routing Platform Hardware Guide Published 2019 10 15 ...
Page 19: ......
Page 86: ......
Page 123: ......
Page 153: ......
Page 239: ...Figure 118 Moving the MX10016 Using a Mechanical Lift g100421 242 ...
Page 240: ...5 CHAPTER Troubleshooting Hardware Restoring Junos OS 245 Alarm Messages 249 ...
Page 241: ......
Page 249: ......
Page 277: ...Restricted Access Warning 281 ...
Page 292: ...Jewelry Removal Warning 296 ...
Page 295: ...Operating Temperature Warning 299 ...
Page 304: ...DC Power Disconnection Warning 308 ...
Page 308: ...DC Power Wiring Sequence Warning 312 ...
Page 311: ...DC Power Wiring Terminations Warning 315 ...
Page 320: ...Translation The emitted sound pressure is below 92 dB A per GR63 CORE 324 ...