Figure 68: Removing an MX10016 Fan Tray Controller
4. Place the fan tray controller in an electrostatic bag or on an antistatic mat.
Installing an MX10016 Fan Tray Controller
Each fan tray of an MX10016 has a fan tray controller (see
). Each controller is a
hot-removable and hot-insertable field-replaceable unit (FRU). You can remove and replace one fan tray
controller while the router is running without turning off power to the router or disrupting routing functions.
Figure 69: Fan Tray Controller
CAUTION:
Do not remove a fan tray controller unless you have a replacement fan tray
controller available.
To access a fan tray controller, you must first remove the associated fan tray. With the fan tray removed,
the fan tray controller is installed horizontally above the Switch Fabric Boards (SFBs) at the top of the
chassis.