background image

Before You Install MWS1000

5

• For DC-power-equipped appliances, you must provide an external certified, dedicated circuit breaker rated

at a minimum of 20 A for each DC power supply.

• For DC-power-equipped appliances, you must supply four DC power cables that meet your local code

requirements.

• You must provide a good earth ground for the rack.

• On DC-power-equipped models, you must supply a ground cable for the power supply. We recommend

using a ground cable identified according to local standards to ground the appliance.

• You must use only copper grounding conductors.

• For a ground wire attaching directly to the rack, we recommend using the following ground lug: Panduit P/N

LCDX8-10A-L, #8 AWG, #10 stud, 0.625-inch spacing.

• To ensure a reliable low-resistance ground bond, you must provide and use star washers and thread-

forming screws with paint-piercing washers to secure the ground wire to the rack frame, and to secure the
appliance chassis to the rack.

• If you connect the ground wire to a ground rail in the rack or to any other grounding facility provided by the

site, you must use the appropriate fasteners to ensure a reliable ground bond. When the ground wire is
attached with bolts or to studs, locking washers can help ensure the ground wire does not come loose.

Summary of Contents for MWS1000

Page 1: ...Mykonos Web Security 4 95 8 Hardware Guide...

Page 2: ...Mykonos Web Security 4 95 8 Hardware Guide This document contains a specification for the MWS1000 hardware appliance as well as instructions for installation into a server environment...

Page 3: ...on 3 2 1 Clearance Requirements for Airflow and Hardware Maintenance for MWS1000 3 2 2 Power Specifications 3 2 3 Unpacking and Inspecting the MWS1000 4 2 4 Before You Install MWS1000 4 3 Installing M...

Page 4: ...n High Availability deployments USB interface One USB port Processor Dual Quad core Intel E5620 2 4Ghz RAM 48 GB DDR3 Storage Six storage drive slots Fans Three 40 mm fans Power supplies Removable AC...

Page 5: ...he MWS1000 has an Input Output Controller with two 10 Gb RJ 45 Ethernet ports labeled 0 and 1 Depending on your order configuration the front panel drive bays may or may not be configured The MWS1000...

Page 6: ...e Maintenance for MWS1000 When planning the installation site allow sufficient clearance around the rack For the cooling system to function properly the airflow around the chassis must be unrestricted...

Page 7: ...ch unit 10 Document any damage noted during your inspection 11 Confirm that the platform has the correct number and type of modules for your ordered configuration If you detect or suspect damage to an...

Page 8: ...only copper grounding conductors For a ground wire attaching directly to the rack we recommend using the following ground lug Panduit P N LCDX8 10A L 8 AWG 10 stud 0 625 inch spacing To ensure a reli...

Page 9: ...0GbE cable into port 0 or 1 on the 10GbE NIC They will be configured as eth4 and eth5 in the setup respectively 10 Power on the appliance When you turn on the power the internal port uses its two LEDs...

Page 10: ...s maintain the proper polarity The power source cables may be labeled and to indicate their polarity There is no standard color coding for DC power cables The color coding used by the external DC powe...

Page 11: ...3 3 RJ 45 Console Connector Pinout Table 3 1 RJ 45 Console Connector Pinout reference Pin Description 1 RTS Output Request to Send 2 DTR Output Data Terminal Ready 3 TxD Output Transmit Data 4 GND Cha...

Reviews: