Connecting DC Power to an EX 3200 or EX 4200 Switch

The power supply in an EX 3200 or EX 4200 switch is a hot-removable and
hot-insertable field-replaceable unit (FRU) located on the rear panel.

Figure 1: DC Power Supply in EX 3200 and EX 4200 Switches

LED-B

LED-A

Terminal block

Locking lever

LEDs

Handle

Fan exhaust

A +

B +

A-

B-

g020202

WARNING:

DC-powered EX 3200 and EX 4200 switches are intended for installation

only in a restricted access location.

Ensure that you have the following parts and tools available to connect DC power to
an EX 3200 or EX 4200 switch:

Electrostatic discharge (ESD) grounding strap

DC power source cables (12–14 AWG) with ring lug (Molex 190700067 or
equivalent) (not provided)

Phillips (+) screwdriver, number 2

Before you begin connecting DC power to an EX 3200 or EX 4200 switch:

Ensure that you have taken the necessary precautions to prevent ESD damage
(see Prevention of Electrostatic Discharge Damage on EX-series Switches).

Ensure that you have connected the switch chassis to earth ground.

CAUTION:

Before you connect power to the switch, a licensed electrician must attach

a cable lug to the grounding and power cables that you supply. A cable with an
incorrectly attached lug can damage the switch (for example, by causing a short
circuit).

To meet safety and electromagnetic interference (EMI) requirements and to ensure
proper operation, you must connect EX 3200 and EX 4200 switches to earth ground
before you connect them to power. For installations that require a separate grounding
conductor to the chassis, use the protective earthing terminal on the switch chassis

Connecting DC Power to an EX 3200 or EX 4200 Switch

1

Summary of Contents for EX 3200

Page 1: ...umber 2 Before you begin connecting DC power to an EX 3200 or EX 4200 switch Ensure that you have taken the necessary precautions to prevent ESD damage see Prevention of Electrostatic Discharge Damage on EX series Switches Ensure that you have connected the switch chassis to earth ground CAUTION Before you connect power to the switch a licensed electrician must attach a cable lug to the grounding ...

Page 2: ...ads is 0 V and that the cable leads will not become active while you are connecting DC power NOTE The DC power supply in EX 3200 and EX 4200 switches has four terminals labeled A A B and B see Figure 1 on page 1 for connecting DC power source cables labeled positive and negative The DC power supplies for EX 3200 and EX 4200 switches are shipped with jumpers from A input to B input tied together an...

Page 3: ...on the power supply terminals in place b Secure the ring lug of the positive DC power source cable to the A or B terminal on the DC power supply c Secure the ring lug of the negative DC power source cable to the A or B terminal on the DC power supply d Tighten the screws on the power supply terminals until snug using the Phillips screwdriver number 2 Do not overtighten apply between 8 lb in 0 9 Nm...

Page 4: ...2 Nm of torque to the screws Figure 3 Securing Ring Lugs to the Terminals on the DC Power Supply in EX 3200 and EX 4200 Switches A B A B LED B LED A g020203 7 Replace the terminal block cover and secure it using the screw Use the Phillips screwdriver number 2 to tighten the screw 8 Close the input circuit breaker 9 Verify that the LEDs on the power supply are lit green and are on steadily DC Power...

Reviews: