Figure 3: Connection diagram for socket outlet combination
(1) Surge protection socket outlet
(4) Socket outlet with normal design
(5) Load
o
Connect surge protection socket outlet according to connection diagram for single socket
outlet (figure 2) or connection diagram for socket outlet combination (figure 3).
i
The maximum continuous voltage (see Technical data) must not be exceeded. In multiple
combinations, when a surge protection socket outlet is used the other socket outlets used
in the combination are also protected in the normal design. For this the socket outlets have
to be installed on the same conductor.
o
Install overvoltage protection socket outlet in appliance box.
o
Mount the cover and frame. Observe correct installation position. Otherwise the LED will
not function.
5 Appendix
5.1 Technical data
Surge protection
Type 3 arrester (one port)
Rated voltage
AC 230 V ~ (± 10%)
Mains frequency
50 / 60 Hz
Maximum continuous voltage
AC 255 V ~ (U
C
)
No-load voltage
4 kV (U
OC
)
Rated load current
16 A (I
L
)
Short circuit strength
1.5 kA (I
SCCR
)
Protection level
L/N
≤ 1.25 kV (F
M
)
L/PE;N/PE
≤ 1.25 kV (F
M
)
TOV characteristic
442 V/5 s/120 min (U
T
)
Circuit breaker
max. 16 A (gG/C)
Ambient temperature
-5 ... +40 °C
Relative humidity
5 ... 95 % (No moisture condensation)
Connection
single stranded
1.5 ... 2.5 mm²
This device can protect connected loads only up to the protection level specified in the technical
data. Surge voltages that are higher than that may still damage the connected devices. The
same applies for devices that require a lower protection level. For this reason we accept no
liability for any damage to the connected loads.
3/4
32515853
J0082515853
05.01.2016
SCHUKO socket with surge voltage protection