Commissioning 

Pushbutton (2) and LED (3) are accessible only during the fitting and 
installation activities, see fig. 

A

For switching over between the two modes of operation press the 
pushbutton (2) for at least 7 s. 
The selected opmode is stored in a non-volatile memory. 
The device is delivered preset to the toggle mode. 

 

 

doorbell mode 

LED (3) lit up red; 

 

the relay contact is closed as long as the 
control pushbutton is kept depressed. 

 

toggle mode 

LED (3) lit up green  

 

the relay contact is closed or opened after 
each press of the control pushbutton. 

 

Response to mains failures 

After a mains failure, all relay contacts are open and must be 
activated again. 

 

Troubleshooting  

If an undefined fault occurs during operation of the device, the 
LED (3) lights up yellow.  
Acknowledge the fault by pressing the pushbutton (2) for ca. 1.5 s. 
The relay station is then in the toggle mode. If necessary, switch over 
to the other opmode, see commissioning. 

 

Technical Data  

 

Rated voltage:   

AC 230 / 240 V ~, 50 / 60 Hz 

 

Operating temperature: 

- 5 °C ... + 45 °C  

 

Storage temperature: 

- 25 °C ... + 70 °C 

 

Fitting width: 

144 mm (8 modules) 

 

Outputs A1 – A8

 

Contact type: 

potential-free n.o. contact (µ contact) 

Switching capacity: 

AC 250 V ~ / 10 A  

Contact rating: 
 

incandescent lamps: 

1400 W 

  HV halogen lamps: 

1225 W 

  conventional transformers: 

1200 VA 

  Tronic transformers: 

1200 VA 

 motors: 

600 

  fluorescent lamps: 

not approved 

  minimum load: 

12 V, 100 mA 

 

Outputs

 

A1‘ – A8‘: 

R

out

 = 330 

Ω

 

DC 24 V / 10 mA max.

 

Switching inputs E1 – E8: 

R

in

 = 200 k

Ω

 

24 V max.

 

Screw terminals 
 

0.5 – 4 mm² single wire 

 

2 x 0.5 – 2.5 mm² single wire 

 

0.34 – 4 mm² stranded without ferrule 

 

0.14 – 2.5 mm² stranded with ferrule 

 

DC output: 

24 V DC, 80 mA

 pushlock 

terminals

 

Power consumption 

 

Typically (all relays on): 

7.7 W

 

Maximum (all outputs at full load) 

12.5 W

 

Standby: 0.5 

W

 

Length of control line:

 

100 m max.

 

Technical specifications subject to change 

 

Please leave these instructions with your customer after installation. 

 

Guarantee 

Our products are under guarantee within the scope of the statutory 
provisions. 

Please return the unit postage paid to our central service 
department giving a brief description of the fault: 

 
 

ALBRECHT JUNG GMBH & CO. KG 
Service-Center 

Kupferstr. 17-19 
D-44532 Lünen 
Service-Line: 

+49 (0) 23 55 . 80 65 53 

Telefax: 

+49 (0) 23 55 . 80 61 65 

E-Mail: [email protected] 

 

Technical matters (general) 

Service-Line: 

+49 (0) 23 55 . 80 65 55 

Telefax: 

+49 (0) 23 55 . 80 62 55 

E-Mail: [email protected] 

 

Technical matters (KNX / EIB) 

Service-Line: 

+49 (0) 23 55 . 80 65 56 

Telefax: 

+49 (0) 23 55 . 80 62 55 

E-Mail: [email protected]

 

 

Reviews: