![Jung KNX 5178TSM-01 Series Operating Instructions Manual Download Page 5](http://html1.mh-extra.com/html/jung/knx-5178tsm-01-series/knx-5178tsm-01-series_operating-instructions-manual_2031812005.webp)
i
If the device does not receive any application software, or the wrong application software,
then the top Status LEDs flash slowly blue and red.
Figure
4
: Activating programming mode
o
Activate programming mode: Press and hold pushbutton at the upper left (12). Then press
pushbutton at the lower right (13).
The top Status LEDs (LED 1 and LED 2) flash quickly blue and red.
o
Load the physical address into the device.
The LEDs return to their previous state – off, on, or flashing slowly.
o
Write the physical address on the device label.
o
Load the application software into the device.
Installing the buttons
The buttons are available as a complete set of buttons (see accessories).
o
Place the buttons on the device in the correct orientation and snap in with a short push.
6 Appendix
Disposal
Please consider your local regulation for disposal and electronic waste recycling.
6.1 Technical data
KNX medium
TP
Commissioning mode
S-mode
Rated voltage KNX
DC 21 ... 30 V SELV
Current consumption KNX
without TSEM
max. 15 mA
with TSEM
max. 20 mA
Connection mode KNX
device connection terminal
Ambient temperature
23 ... 113 °F
(-5 ... +45 °C)
Storage/transport temperature
-13 ... +158 °F
(-25 ... +70 °C)
Protection class
III
Connection of the extension module
Number
1
Cable length
100 ft (30 m)
Cable type
Use only cables which are approved for KNX.
5/6
Room temperature controller module 2-gang
32589705
J0082589705
28.06.2017