Art. No. 5071 TSM
Art. No. 5072 TSM
Art. No. 5073 TSM
Art. No. 5074 TSM
2.4 Commissioning
After connection and mounting, the pushbutton sensor module can be put into operation. The
start-up procedure is basically confined to programming with the ETS and attaching the
decorative control surfaces.
i
The extension module does not receive any physical address of its own. It is activated by
the application program loaded in the basic module.
Programming the physical address
The pushbutton sensor does not have a separate programming button or LED. Programming
mode is activated by a defined and time-delayed press of the upper left and lower right of the
pushbutton. Programming mode is signalled by flashing operation LED. To program the
physical address, the decorative control surfaces can be snapped onto the device.
(26)
(27)
Figure 6: Buttons for activating Programming mode
i
If the device does not receive any application software, or the wrong application software,
then the operation LED (Colour: blue) flashes slowly.
For commissioning, the pushbutton sensor module must be connected and the bus voltage
switched on.
o
Activate Programming mode. Press button at the top left (26) and keep it depressed
(figure 6). Then press second push-button at the lower right (27).
Programming mode is activated. The operation LED (26) flashes quickly (approx. 8 Hz).
i
Use suitable objects to push the buttons (e.g. thin screwdriver, tip of a ballpoint pen, etc.)
i
To exclude any inadvertent activation of Programming mode during a 'normal' use of the
control surface in later operation, the time between the first and the second button
actuation must be at least 200 ms. Pressing both buttons simultaneously (time between
first and second actuation < 200 ms) will not result in an activation of Programming mode.
i
In programming mode, the operation LED flashes steadily in the colour blue. The flashing
rate remains the same until the operating mode is ended. The state of the LED defined by
Programming mode will always prevail.
o
Program the physical address with the help of the ETS.
o
Programming mode ends:
- Automatically after adoption of the physical address
- By pressing a button
Page 9 of 39
Installation, electrical connection and operation