Jung KNX 230011 SU Quick Start Manual Download Page 6

Switch actuator, 1-gang

Load physical address and application program using the ETS.

Safe-state mode

The safe state mode stops the execution of the loaded application program.

Only the system software of the device is still functional. ETS diagnosis functions and pro-
gramming of the device are possible.

Activating the safe-state mode

Switch off the bus voltage or disconnect the device from the KNX.

Wait about 10 s.

Press and hold down the programming button.

Switch on the bus voltage or connect the device to KNX. Release the programming button
only after the programming LED starts flashing slowly.
The safe-state mode is activated.

With a new brief press of the programming button, the programming mode can be
switched on and off as usual also in the safe-state mode. If Programming mode is active,
the programming LED stops flashing.

Deactivating safe-state mode

Switch off bus voltage (wait approx. 10 s) or carry out ETS programming.

Master reset

The master reset restores the basic device setting (physical address 15.15.255, firmware re-
mains in place). The device must then be recommissioned with the ETS.

During secure operation: A master reset deactivates device security. The device can then be re-
commissioned with the device certificate.

Performing a master reset

Precondition: The safe-state mode is activated.

Press and hold down the programming button for > 5 s.
The programming LED flashes quickly.

The device performs a master reset, restarts and is ready for operation again after ap-
prox. 5 s.

Restoring the device to factory settings

Devices can be reset to factory settings with the Jung ETS Service App. This function uses the
firmware contained in the device that was active at the time of delivery (delivery state). Restor-
ing the factory settings causes the devices to lose their physical address and configuration.

5

Technical data

Ambient conditions
Ambient temperature

-5 ... +45 °C

Storage/transport temperature

-25 ... +70 °C

Dimensions (W × H × D)

48 x 50 x 28 mm

KNX
KNX medium

TP256

Commissioning mode

S-mode

Rated voltage KNX

DC 21 ... 32 V SELV

Current consumption KNX

5 ... 18 mA

Connection mode KNX

Connection terminal on control cable

Outputs

6 / 8

82404303

28.01.2021

J0082404303

Summary of Contents for KNX 230011 SU

Page 1: ...stallation that there is always sufficient insula tion between the mains voltage and the bus A minimum distance of at least 4 mm must be maintained between bus conductors and mains voltage cores Danger of electric shock on the KNX installation Do not connect any external voltage to the in puts The device might be damaged and the SELV potential on the KNX bus line will no longer be available These ...

Page 2: ...pula tion in building automation and can be configured in the ETS project Detailed specialist know ledge is required A device certificate which is attached to the device is required for safe com missioning During mounting the certificate must be removed from the device and stored se curely Planning installation and commissioning of the device are carried out with the aid of the ETS version 5 7 3 a...

Page 3: ...on Disabling functions Debounce time adjustable Logic function characteristics logic gates Transformer conversion Disabling element comparator Limit value switch 4 Information for electrically skilled persons DANGER Mortal danger of electric shock Disconnect the device Cover up live parts 4 1 Fitting and electrical connection DANGER When connecting the bus extensions and mains voltage wires in a s...

Page 4: ...tronic device box with partition Ob serve cable routing and spacing Figure 3 Figure 3 Mounting example in electronic device box with partition wall series push button and NTC temperature sensor 5 Appliance box 6 Partition 7 potential free contacts e g series push button 8 NTC temperature sensor optional Figure 4 Cable spacing Minimum spacing between the mains voltage and bus extension wires 4 mm F...

Page 5: ...her with COM connections of other devices 4 2 Commissioning Commissioning the device NOTICE Undefined relay state at delivery Unexpected control of connected loads During commissioning before switching on the load ensure that all relay contacts are open by applying the KNX bus voltage Observe commissioning sequence Switch on the KNX bus voltage Wait about 10 s Connect the load circuit Delivery sta...

Page 6: ...vice setting physical address 15 15 255 firmware re mains in place The device must then be recommissioned with the ETS During secure operation A master reset deactivates device security The device can then be re commissioned with the device certificate Performing a master reset Precondition The safe state mode is activated Press and hold down the programming button for 5 s The programming LED flas...

Page 7: ...nsated 1160 W 140 μF Fluorescent lamps T5 T8 twin lamp circuit 2300 W 140 μF Mercury vapour lamps uncompensated 1000 W Mercury vapour lamps parallel compensated 1160 W 140 μF Reduction of switching current per 5 C in excess of 35 C 10 when installed in wooden or dry construction walls 15 when installed in multiple combinations 20 Clampable conductor cross section single stranded 0 5 4 mm Finely st...

Page 8: ...ovided in accordance with statutory requirements via the specialist trade ALBRECHT JUNG GMBH CO KG Volmestraße 1 58579 Schalksmühle GERMANY Telefon 49 2355 806 0 Telefax 49 2355 806 204 kundencenter jung de www jung de 8 8 82404303 28 01 2021 J0082404303 ...

Reviews: