5 Appendix
5.1 Status LED
Off
No power supply
Orange / on
Module scan via analog input
Orange / flashes quickly (2/s)
Analog input module scan
Red / flashes slowly (1/s)
Error: Undervoltage at the module connection
/ short-circuit Us
Red / flashes quickly (2/s)
Error: No project / error in programming
Green / flashes slowly (1/s)
Address assignment, module scan completed,
project design OK
Green / flashes quickly (2/s)
Parameter download to module
Green / on
Module scan completed, everything OK
Disposal
Please consider your local regulation for disposal and electronic waste recycling.
5.2 Technical data
Supply
Power supply
AC 24 V
Current consumption
max. 250 mA
Ext. sensors (+Us)
24 V DC, max. 100 mA
Module connection
24 V DC, max. 80 mA
KNX
KNX medium
TP
Commissioning mode
S-mode
Rated voltage KNX
DC 21 ... 30 V SELV
Ambient conditions
Ambient temperature
23 ... 113 °F
(-5 °C ... +45 °C)
Storage/transport temperature
-13 ... 158 °F
(-25 ... +70 °C)
Relative humidity
max. 93%
Housing
Fitting width
72 mm / 4 modules
Connections
Inputs, supply
Screw terminals
Single stranded
20 ... 12 AWG
(0.5 ... 4 mm²)
Finely stranded (without conductor sleeve)
22 ... 12 AWG
(0.34 ... 4 mm²)
Finely stranded (with conductor sleeve)
26 ... 14 AWG
(0.14 ... 2.5 mm²)
Extension module
6-pin system connector
Sensor inputs
Number
4 x analog
Evaluable sensor signals
Voltage signals
0 ... 1 V DC or
0 ... 10 V DC
Current signals
0 ... 20 mA DC or
4 ... 20 mA DC
Impedance sensor signals
Voltage measurement
approx. 18 kOhm
Measuring current
approx. 100 Ohm
6/7
4-channel analog input
32551515
J0082551515
08.11.2017