5 Appendix

5.1 Status LED

 Off

No power supply

Orange / on

Module scan via analog input

Orange / flashes quickly (2/s)

Analog input module scan

Red / flashes slowly (1/s)

Error: Undervoltage at the module connection
/ short-circuit Us

Red / flashes quickly (2/s)

Error: No project / error in programming

Green / flashes slowly (1/s)

Address assignment, module scan completed,
project design OK

Green / flashes quickly (2/s)

Parameter download to module

Green / on

Module scan completed, everything OK

Disposal

Please consider your local regulation for disposal and electronic waste recycling.

5.2 Technical data

Supply
Power supply

AC 24 V

Current consumption

max. 250 mA

Ext. sensors (+Us)

24 V DC, max. 100 mA

Module connection

24 V DC, max. 80 mA

KNX
KNX medium

TP

Commissioning mode

S-mode

Rated voltage KNX

DC 21 ... 30 V SELV

Ambient conditions
Ambient temperature

23 ... 113 °F

(-5 °C ... +45 °C)

Storage/transport temperature

-13 ... 158 °F

(-25 ... +70 °C)

Relative humidity

max. 93%

Housing
Fitting width

72 mm / 4 modules

Connections
Inputs, supply

Screw terminals

Single stranded

20 ... 12 AWG
(0.5 ... 4 mm²)

Finely stranded (without conductor sleeve)

22 ... 12 AWG

(0.34 ... 4 mm²)

Finely stranded (with conductor sleeve)

26 ... 14 AWG

(0.14 ... 2.5 mm²)

Extension module

6-pin system connector

Sensor inputs
Number

4 x analog

Evaluable sensor signals
Voltage signals

0 ... 1 V DC or

0 ... 10 V DC

Current signals

0 ... 20 mA DC or

4 ... 20 mA DC

Impedance sensor signals
Voltage measurement

approx. 18 kOhm

Measuring current

approx. 100 Ohm

6/7