Light scene operation possible 

2-point light control in combination with a radio presence detector possible 

Run-on time of approx. 1 minute in connection with radio motion detectors. 

4 Operation 

Operation with radio transmitter 

A radio transmitter has to be taught in order to be able to operate the switch actuator. 

Observe the instructions for the radio transmitter. 

Operation on the device 

Outputs A1 to A4 can be switched on or off locally by pressing the programming buttons briefly. 
The switching position of the individual channels is indicated by the 4 LEDs. 

Press the programming button (3) of the desired output briefly. 
The assigned output is switched on or off. 

5 Information for electrically skilled persons 

5.1 Fitting and electrical connection 

DANGER! 
Electrical shock when live parts are touched. 
Electrical shocks can be fatal. 
Before carrying out work on the device or load, disengage all the 
corresponding circuit breakers. Cover up live parts in the working environment. 

Connecting and mounting the switch actuator 

Figure 2 

The total length of the bus cables between the RMD devices may not exceed 3 m. 

The polarity of the bus cables must not be reversed. 

For the bus cable, use a shielded cable with twisted conductors and a conductor diameter 
of 0.8 mm that is designed for a test voltage of 2.5 kV AC. Examples of permissible bus 
cables are YCM 2×2×0.8 or J-Y(St)Y 2×2×0.8. 

Mount switch actuator (1) on DIN rail. 