Art. No. DS 4092 TS
4.2.4.1.5 Push-button function Scene extension
The ETS indicates the "Function" parameter if the function of the push-button is set to "scene
extension". A distinction is then made between the following settings…
-
"Scene extension without storage function",
-
"Scene extension with storage function",
In the scene extension function, the device transmits a preset scene number (1…64) via a
separate communication object to the bus after a button-press. This feature permits recalling
scenes stored in other devices and also storing them, if the storage function is used.
In the setting "Scene extension without storage function", a button-press triggers the simple
recall of a scene. A long button-press has no further or additional effect.
In the setting "Scene extension with storage function", the device monitors the length of the
actuation. A button-press of less than a second results in a simple recall of the scene as
mentioned above. After a button-press of more than five seconds, the device generates a
storage instruction whereby a storage telegram is transmitted to the bus. An operation lasting
between one and five seconds will be discarded as invalid.
The parameter "Scene number specifies which of the maximum of 64 external scenes is to be
activated after a button-press.
Page 44 of 143
Software "Rotary sensor with extensions 10FE1x"
Functional description