Jung DALI 240 PDPE Operation Manual Download Page 3

Connecting and mounting the device 

picture 2 

(1)  DALI potentiometer "Active mode" 
(6)  DALI subscriber e. g. DALI electrical ballast 
(7)  DALI potentiometer without connection of mains voltage "Passive mode" 

Connect the DALI potentiometer and DALI electrical ballast according to the wiring 
example (picture 2). In so doing, observe the data of the electrical ballast manufacturer. 

When switch multiple DALI potentiometers, ensure correct polarity. 

If multiple miniature circuit breakers supply dangerous voltages to the device or load, 
couple the miniature circuit breakers or label them with a warning, to ensure release is 
guaranteed. 

Ensure that the control cable is of the appropriate type, cross-section and routing for the 
VDE specifications for 250 V cable, control voltage has basic insulation. 

The control cable and load cable can be run in a shared cable, e.g. NYM J 5×1.5. 

The connected DALI subscribers may be operated on different phases. 

5.2 Commissioning 

Saving a basic brightness 

The basic brightness should be a state when turning the DALI potentiometer does not directly 
lead to an increase in brightness. 

Switch the lighting on minimum brightness. 

Turn the DALI potentiometer to the point that where the brightness begins to increase. 

Press the control knob for longer than 10 seconds. 
The lighting switches briefly off and on again. The basic brightness is saved. 

Any basic brightness can be saved from which it is possible to add brightness. 

Deleting the basic brightness 

Switch the lighting off. 

Press the control knob for longer than 10 seconds. 
Briefly switch the lighting to maximum brightness and then off again. The basic brightness 
has been deleted. 

DALI subscribers of different manufacturers may deviate from the acknowledgements 
given here. 

3/4 

82563213 
J:0082563213 

06.05.2010 

Power DALI potentiometer insert 

Reviews: