Universal automatic switch 1.1 m
■
Press the programming button.
The red LED in the lens lights up.
■
Assign physical address.
The red LED goes out.
■
Write the physical address on the device label.
■
Load the application program into the device.
In case of active temperature measurement ("Universal" version) compare the tempera-
ture measurement.
Test the detection area
In the case of main units and extensions, check the detection areas of the devices individually.
Precondition: The device is installed and connected. The physical address is loaded.
■
Activate walking test:
Activate the parameter "Walking test after ETS programming" and download the applica-
tion software.
The device now operates brightness-independently. The PIR sensors are active accord-
ing to their programmed sensitivity.
■
Pace off the detection field, paying attention to reliable detection and interference
sources.
Any motions detected are displayed by the blue LED.
■
Limit the detection area as required. Adjust sensitivity with adjuster Sens. or IR remote
control, or change the programming.
■
Deactivate the parameter "Walking test after ETS programming" and download the appli-
cation software.
If enabled, the walking test function can be activated with the button Test of the IR remote
control.
Locking the slide switch
Figure
18
: Locking the slide switch
The slide switch can be mechanically locked to the AUTO position as required. Use the pro-
vided locking screw for this.
■
Remove the cover from the slide switch (5) (Figure
■
Move slide switch to AUTO position.
■
Screw the locking screw (10) in the hole (9) of the slide switch (Figure
■
Carefully reattach the cover.