Jung 3210 UP Operating Instructions Manual Download Page 5

Function of Inputs 1 and 2 in the as-delivered state 

Input 

NO contact 

Output 

Press briefly 

Light on 100% 

Press for a long time 

Dimming brighter 

Press briefly 

Light off 

Press for a long time 

Dimming darker 

4.2 Commissioning 

Load the address and the application software 

Switch on the bus voltage 

Assign physical addresses and load application software into the device. 

Note the physical address on the device label. 

5 Appendix 

5.1 Technical data 

Rated voltage 

AC 230 V ~ 

Mains frequency 

50 / 60 Hz 

Ambient conditions 
Ambient temperature 

-5 ... +45 °C 

Storage/transport temperature 

-25 ... +70 °C 

Contact type 

ε, MOSFET 

Connected load 
Incandescent lamps 

50 ... 210 W 

HV halogen lamps 

50 ... 210 W 

Inductive transformers 

50 ... 210 VA 

Tronic transformers 

50 ... 210 W 

Mixed loads 
Ohmic-inductive 

50 ... 210 VA 

ohmic-capacitive 

50 ... 210 W 

capacitive-inductive 

not permitted 

Control cable and inputs 
Control cable (preterminated) 

YY6x0.6 

Input type 

Potential-free 

Total length of extension unit cable 

max. 5 m 

Poll voltage, extension inputs 

approx. 5 V 

Dimensions Ø×H 

53×28 mm 

Connection mode 

Screwless terminal (enclosed) 

Single stranded 

1.0 ... 2.5 mm² 

KNX 
KNX medium 

TP 1 

Commissioning mode 

S-mode 

Rated voltage KNX 

DC 21 ... 32 V SELV 

Power consumption KNX 

typical 150 mW 

Connection mode KNX 

Connection terminal on control cable 

5.2 Troubleshooting 

Light has switched off 

Cause 1: short-circuit in output circuit. 

Disconnect device from mains; switch off associated circuit breakers.  
Eliminate short-circuit. 
Switch mains voltage on again. 

5/7 

82576313 
J:0082576313 

06.01.2012 

Flush-mounted dimming actuator, 1-gang, with satellite input 

Summary of Contents for 3210 UP

Page 1: ...witched off Danger of electric shock Before working on the device or before exchanging light bulbs disconnect mains voltage and switch off circuit breakers Do not connect any lights with integrated di...

Page 2: ...bsite Intended use Switching and dimming of incandescent lamps 230 V halogen lamps and LV halogen lamps with inductive transformers or Tronic transformers Installation in appliance box to DIN 49073 Pr...

Page 3: ...ance box the KNX bus line may come into contact with the mains voltage This endangers the safety of the entire KNX installation People at remote devices may also receive an electric shock Do not place...

Page 4: ...dimmable inductive transformers CAUTION Danger of destruction from mixed loads The dimmer and load may be destroyed Do not connect capacitive loads e g electronic transformers and inductive loads e g...

Page 5: ...ansformers 50 210 VA Tronic transformers 50 210 W Mixed loads Ohmic inductive 50 210 VA ohmic capacitive 50 210 W capacitive inductive not permitted Control cable and inputs Control cable preterminate...

Page 6: ...re Check mains voltage Cause 6 overheating protection has tripped due to overload or too high ambient temperature Disconnect device from mains switch off associated circuit breakers Let device cool do...

Page 7: ...kundencenter jung de General equipment Service Line 49 0 23 55 80 65 55 Telefax 49 0 23 55 80 62 55 kundencenter jung de KNX equipment Service Line 49 0 23 55 80 65 56 Telefax 49 0 23 55 80 62 55 kund...

Reviews: