Flush-mounted dimming actuator, 1-gang, with satellite input 

Flush-mounted dimming actuator, 1-gang, with satellite input 

Art.-No.: 3210 UP 

Operating instructions 

1 Safety instructions 

Electrical equipment may only be installed and fitted by electrically skilled persons. 

Failure to observe the instructions may cause damage to the device and result in fire and 
other hazards. 

Danger of electric shock on the KNX installation. Do not connect any external voltage to 
the inputs. Doing so may damage the device(s), and the SELV potential on the KNX bus 
line will no longer be available. 

Danger of electric shock. Device is not suitable for disconnection from supply voltage. 
The load is not electrically isolated from the mains even when the device is switched off. 

Danger of electric shock. Before working on the device or before exchanging light bulbs, 
disconnect mains voltage and switch off circuit breakers. 

Do not connect any lights with integrated dimmers. Device can be damaged. 

Do not connect any electronic lamps, e.g. switchable or dimmable compact fluorescent 
lamps or LED lamps. Device can be damaged. 

Fire hazard. For operation with inductive transformers, each transformer must be fused 
on the primary side in accordance with the manufacturer's instructions. Only safety 
transformers according to EN 61558-2-6 may be used. 

These instructions are an integral part of the product, and must remain with the end 
customer. 

2 Device components 

Figure 1: Flush-mounted dimmer actuator 

(1)  Control cable 
(2)  Programming button and LED 
(3)  Connection of mains and power cables 

Connection assignment, power cables 

BK, black: connection conductor 

BN, brown: dimming output 

1/7 

82576313 
J:0082576313 

06.01.2012 

Summary of Contents for 3210 UP

Page 1: ...witched off Danger of electric shock Before working on the device or before exchanging light bulbs disconnect mains voltage and switch off circuit breakers Do not connect any lights with integrated di...

Page 2: ...bsite Intended use Switching and dimming of incandescent lamps 230 V halogen lamps and LV halogen lamps with inductive transformers or Tronic transformers Installation in appliance box to DIN 49073 Pr...

Page 3: ...ance box the KNX bus line may come into contact with the mains voltage This endangers the safety of the entire KNX installation People at remote devices may also receive an electric shock Do not place...

Page 4: ...dimmable inductive transformers CAUTION Danger of destruction from mixed loads The dimmer and load may be destroyed Do not connect capacitive loads e g electronic transformers and inductive loads e g...

Page 5: ...ansformers 50 210 VA Tronic transformers 50 210 W Mixed loads Ohmic inductive 50 210 VA ohmic capacitive 50 210 W capacitive inductive not permitted Control cable and inputs Control cable preterminate...

Page 6: ...re Check mains voltage Cause 6 overheating protection has tripped due to overload or too high ambient temperature Disconnect device from mains switch off associated circuit breakers Let device cool do...

Page 7: ...kundencenter jung de General equipment Service Line 49 0 23 55 80 65 55 Telefax 49 0 23 55 80 62 55 kundencenter jung de KNX equipment Service Line 49 0 23 55 80 65 56 Telefax 49 0 23 55 80 62 55 kund...