Connecting and mounting the control unit.
picture 2: Connection diagram, single-phase
picture 3: Connection diagram, three-phase
(1) Control unit
(5) Lamp operating device with 1-10 V interface, electronic ballast
(6) Installation button, NO contact
i
The load output is not protected internally. For device protection, connect a 10 A miniature
circuit breaker upstream.
i
Control cable: appropriate type, cross-section and routing for the VDE specifications for
250 V cables, control voltage has basic insulation. The control cable and load cable can be
run in a shared cable, e.g. NYM J 5 x 1.5. Connect lamp operating device and electronic
ballast with earth conductor in accordance with the manufacturer's instructions.
i
The maximum number of lamp operating devices that can be controlled by the control unit
is the sum of the control currents I
1
+ I
2
+ I
3
(picture 2) and I (picture 3)(see chapter 6.1.
Technical data). For the control current of the lamp operating devices, see the information
provided by the manufacturer.
3/5
82515713
J:0082515713
13.08.2010
Light Management
Push-button controller, built-in