Characteristics of 24 V binary input 

AC and DC voltages can be connected 

Separate reference potentials for inputs 

E1...E3

 and 

E4...E6 

4 Information for electrically skilled persons 

4.1 Fitting and electrical connection 

DANGER! 
Electrical shock when live parts are touched. 
Electrical shocks can be fatal. 
Before carrying out work on the device or load, disengage all the 
corresponding circuit breakers. Cover up live parts in the working environment. 

Fitting the device 

Observe the temperature range. Ensure adequate cooling. 

Mount device on DIN rail. 

Connect 230 V binary inputs 

Figure 3: Connection example for 230 V binary inputs 

Connect device as shown in the connection example (figure 3). Connect reference 
potential 

N

 separately for each input. 

3/7 

82540413 
J:0082540413 

06.08.2013 

Binary input 

Summary of Contents for 2114 REG

Page 1: ...killed persons Failure to observe the instructions may cause damage to the device and result in fire and other hazards Danger of electric shock Do not connect FELV and SELV PELV systems together When...

Page 2: ...out with the aid of KNX certified software The latest versions of product database and the technical descriptions are available on our website Intended use Polling of conventional switching or push b...

Page 3: ...tal Before carrying out work on the device or load disengage all the corresponding circuit breakers Cover up live parts in the working environment Fitting the device Observe the temperature range Ensu...

Page 4: ...4 Common reference potential for inputs E1 E3 and E4 E6 Installing the cover It is necessary to install a cover to protect the bus connection against hazardous voltages in the connection area Figure 5...

Page 5: ...oval VDE KNX KNX medium TP 1 Commissioning mode S mode Rated voltage KNX DC 21 32 V SELV Power consumption KNX max 150 mW Connection type for bus Connection terminal Ambient temperature 5 45 C Storage...

Page 6: ...modules Power loss max 3 4 W Connection single stranded 0 5 4 mm finely stranded without conductor sleeve 0 5 4 mm finely stranded with conductor sleeve 0 5 2 5 mm Cable length max 100 m Binary input...

Page 7: ...gress We provide a warranty as provided for by law Please send the device with a description of the defect to our central customer service office ALBRECHT JUNG GMBH CO KG Volmestra e 1 58579 Schalksm...

Reviews: