Light Management
Tronic switching insert
Ref.-no.:1254TSE
Depending upon the type of installation, the maximum connected load
must be reduced by:
- 6.5 % per 5 °C exceeding of the ambient temperature of 25°C.
- 15% for installation in wooden, gypsum plaster or hollow walls.
- 20% for installation in multiple combinations.
Note the technical connection conditions of the power stations.
7. The Use of Extensions
Connect several extensions as shown in Fig. C.
Fig. C
Connect several extensions as shown in Fig. C.
Control from an extension unit is possible only if the attachment on the
main unit is in place.
Tronic switching insert
g
"2-wire" extension insert
h
Connection of further extensions
i
Load
j
"2-wire" extension insert:
Using the short-stroke key leads to
the same functionality as on the
Tronic switching insert.
Mechanical push-button (n. o. contact): ON/OFF (toggling)
Illuminated mechanical pushbuttons must have a separate N terminal.
8. Technical
specifications
Nominal voltage:
AC 230 V ~, 50 / 60 Hz
Operating temperature:
-20 °C ... +45 °C
Connected load:
50 - 420 W/VA
- Incandescent lamps
- HV halogen lamps
- Tronic transformers
Number of Extensions:
"2-wire" extension insert,
mechanical push-button:
unlimited
"3-wire" extension insert:
10
Different types of extension units can be combined
Total length of extension connecting cable:
max. 100 m
3