7 Malfunctions/faults
7
Malfunctions/faults
DANGER!
Medium residue may cause damage to humans, the environment, and equipment!
CAUTION!
Irreparable damage occurs if the membrane comes into contact with sharp or hard objects!
Type of fault
Possible causes
Measures
No measuring and/or output
signal
Voltage supply is too low
Check the voltage supply,
chapter 5 "Technical data", page 19
Open circuit, incorrect connection
Check connecting cables
chapter 5 "Technical data", page 19
Mechanical, thermal, or chemical dam-
age of the level probe
Send the device with the fault description
and declaration of decontamination to the
suppliers
Constant output signal even
with changes in pressure
Measuring system destroyed by excess
pressure
Send the device with the fault description
and declaration of decontamination to the
suppliers
Output signal is distorted as a result of
excess pressure due to current limiting
Check voltage supply,
chapter 5 "Technical data", page 19
Output signal is too high
Measuring range selected is too small
Send the device with the fault description
and declaration of decontamination to the
suppliers
Electrics are faulty
Voltage supply is too high
Output signal is too low
For current output signal:
Burden is too high
Change the burden,
chapter 5 "Technical data", page 19
Voltage supply is too low
Change the voltage supply,
chapter 5 "Technical data", page 19
Membrane damaged by mechanical in-
fluences, an aggressive medium, or cor-
rosion, for example
Send the device with the fault description
and declaration of decontamination to the
suppliers
Varying
zero point signal
Medium and/or ambient temperature is
too high or too low
Send the device with the fault description
and declaration of decontamination to the
suppliers
Membrane contaminated
Carefully clean the membrane using a soft
brush or sponge with a non-aggressive
cleaning agent, for example,
chapter 6.2 "Maintenance", page 22
Membrane damaged by mechanical in-
fluences, an aggressive medium, or cor-
rosion, for example
Send the device with the fault description
and declaration of decontamination to the
suppliers
Moisture entered the device
Characteristic line of the out-
put signal is not linear
Device altered by inadmissible operating
conditions (such as excess pressure)
Send the device with the fault description
and declaration of decontamination to the
suppliers
Summary of Contents for MAERA S29 SW
Page 2: ......
Page 3: ...40439300T94Z000K000 DE 00638282 JUMO MAERA S29 SW Pegelsonde aus Titan Montageanleitung...
Page 4: ......
Page 6: ...Inhalt 9 Baumusterpr fbescheinigung 28 10 DNV GL Zulassung 32 11 China RoHS 35...
Page 30: ...28 9 Baumusterpr fbescheinigung 9 Baumusterpr fbescheinigung...
Page 31: ...29 9 Baumusterpr fbescheinigung...
Page 32: ...9 Baumusterpr fbescheinigung 30...
Page 33: ...31 9 Baumusterpr fbescheinigung...
Page 38: ...11 China RoHS 36...
Page 39: ......
Page 42: ......
Page 44: ...Contents 9 Examination certificate 28 10 DNV GL Approval 32 11 China RoHS 35...
Page 68: ...28 9 Examination certificate 9 Examination certificate...
Page 69: ...29 9 Examination certificate...
Page 70: ...9 Examination certificate 30...
Page 71: ...31 9 Examination certificate...
Page 76: ...11 China RoHS 36...
Page 77: ......
Page 79: ...40439300T94Z000K000 FR 00638282 JUMO MAERA S29 SW Sonde de niveau en titane Notice de montage...
Page 80: ......
Page 82: ...Sommaire 9 Certificat d examen de type CE 29 10 Homologation DNV GL 33 11 China RoHS 36...
Page 107: ...29 9 Certificat d examen de type CE 9 Certificat d examen de type CE...
Page 108: ...9 Certificat d examen de type CE 30...
Page 109: ...31 9 Certificat d examen de type CE...
Page 110: ...9 Certificat d examen de type CE 32...
Page 115: ......
Page 117: ......
Page 118: ......