7 Technical data
28
Screen
Electrical data
Environmental influences
Housing
Resolution
320 x 240 pixels
Size
5.7"
Number of colors
27 colors
Supply
(switch-mode power supply)
110 — 240V AC +10/-15%, 48 — 63Hz or
20 — 30V AC/DC, 48 — 63Hz
Electrical safety
Test voltages (type test)
- mains supply circuit to
measuring circuit
- mains supply circuit to housing
(protective conductor)
- measuring circuits to
measuring circuit and housing
- electrical isolation between
the analog inputs
to EN 61 010, Part 1 of August 2002
overvoltage category II, pollution degree 2
with AC supply: 3.7kV/50Hz, 1min,
with AC/DC supply: 510V/50Hz, 1min
with AC supply: 2.3kV/50Hz, 1min,
with AC/DC supply: 510V/50Hz, 1min
510V/50Hz, 1min
up to 30V AC and 50V DC
Supply voltage error
< 0.1% of range span
Power consumption
approx. 25VA
Electrical connection
at rear by plug-in screw terminals,
max. conductor cross-section 2.5mm
2
or 2x 1.5mm
2
with ferrules
Ambient temperature range
0 to +45°C
Ambient temperature error
0.03% per °C
Storage temperature range
-20 to +60°C
Climatic conditions
≤
75% rel. humidity, no condensation
EMC
- interference emission
- immunity to interference
EN 61 326
Class A
to industrial requirements
Housing front
zinc die-casting or stainless steel
Housing type
panel-mounting housing to DIN 43 700,
galvanized steel sheet
Bezel size
200mm x 144mm
Depth behind panel
233mm
Panel cut-out
138
+1.0
mm x 138
+1.0
mm
Housing fixing
in panel to DIN 43 834
Operating position
unrestricted, taking into account the viewing angle of the screen,
horizontal ±50°,
vertical ±30°
Protection
to EN 60 529 Category 2,
front IP54 (IP65 with extra code stainless steel front),
rear IP20
Weight
approx. 3.5kg