81
9 Maintenance
Orange
4 to 20 mA
Switched
DISP.OVF
The measured flow
rate display in the
process level is full
and does not corre-
spond to the actual
flow rate.
•
Change the unit or dec-
imal places in the UNIT
function in the parame-
ters menu so that the
display can show high-
er values
Apart from the dis-
play, the device is
working in line with
the actual value for
the flow rate.
Orange
4 to 20 mA
Switched
LIN.LOST
The factory calibra-
tion has been lost.
•
Contact manufacturer
The device is mea-
suring the wrong
values.
Orange
4 to 20 mA
Switched
CAL.FAIL
Calibration of the
flow rate zero point
failed.
•
Refer to the conditions
for calibration,
see
chapter 8.7.2 "Calibrat
e the flow rate zero
point", page 67
a
If the output has been configured to switch upon generation of a warning,
see chapter 8.6.5 "Configuring out-
Device sta-
tus LED
Analog out-
put AO1
Digital outputs
DO1/DO2/DO3
Displayed
message
Meaning
Measure