6 Operation
36
6.8
MANUAL mode/Simulation mode
These functions can be used to set the switching outputs and analog outputs
of the instrument manually to a defined state. This facilitates dry startup,
troubleshooting and customer service, etc.
.
Simulation mode accesses the analog outputs and binary outputs directly.
When simulation mode has been selected, MANUAL mode is not possible!
In MANUAL mode the settings for "higher order controllers" are taken into
consideration.
6.8.1
MANUAL mode only via "higher order" controller functions
Select Manual mode
✱
Set ADMINISTR.-LEVEL/PARAMETER LEVEL/CONTROLLER/CTRL.SPEC.
FUNCT./MANUAL MODE "Locked, Coding or Switching.
Locked =
No Manual mode, control is via device.
Coding =
The outputs are active as long as the
or
key is pressed.
Switching = the outputs are active if the
or
key is pressed. If the
corresponding key is pressed again, the output becomes inactive
again.
Simulation mode
MANUAL mode
"Higher order"
controller
Binary outputs
Analog outputs
In the factory setting of the instrument the MANUAL mode parameter is locked
and can only be activated by the administrator!
This parameter must first be released for other users, see "Release level",
page 32.